Auber Instruments SYL-1813 Руководство по эксплуатации
Просмотреть онлайн или скачать pdf Руководство по эксплуатации для Измерительные приборы Auber Instruments SYL-1813. Auber Instruments SYL-1813 2 страницы. Multifunction autometer
AUBER INSTRUMENTS
Instruction Manual
A. Specifications
◆Power supply: DC12V (isolated)
◆Power consumption: <2W
◆Sampling rate: 4 samples/sec
◆Accuracy: 0.2% full scale ±1
◆
:
Display range -1999 9999
◆
Relay contact rating 3A @ 220VAC
◆
Outside dimensions 48×24×75mm
◆
Mounting cutout dimension 45×22mm
◆
:
LED display 0.28" red color
◆
Working condition 0 50
B. Front Panel
AUBER1812
6
2008
5
MAX
(MIN)
4
① Alarm and relay J1 indicator
② Up key
③ Shift key
④ Set key
⑤ Maximum and Minimum value indicator
⑥ Display window
1. AL on indicates alarm is on and J1 relay is pulled in (closed).
2.MAX(MIN) on when Display window shows the maximum value or the
time of the Max. MAX(MIN) blinking when Display window shows the
minimum value or the time of Min.
3. ">" shift key: In the parameter setting mode, press this key to select the
digit to be changed. In the normal operation mode, press this key to
change the display in the sequence as shown in the diagram below.
"
>
"
X X X . X
X X X . X
Process value
Maximum
( P V )
( M A )
Max (Min) off
Max (Min) on
"
>
"
X X .X X
Min time
Max (Min) blink
Please note that time is expressed in hour.minute (hh.mm) format.
4." " up key . In the parameter setting mode, press it to increase the
Λ
displayed value. When displaying Max/Min, press and hold it for 3 seconds
to clear the Max/Min stored. In normal function, this key has two functions,
show operation time and change display brightness. Press and hold it
down to show the operation time since on. Release the key to show the
current temperature (process value). Each time the key is pressed, the
display brightness will also be changed from bright to dim or from dim to
bright.
2013.05
SYL-1813 Multifunction Autometer
~
:
:
:
: ~
℃ , ≤
85%RH
1
3
2
"
>
"
X X .X X
Max time
( M A _ t )
Max (Min) on
"
>
"
X X X . X
Minimum
( M I )
( M I _ t )
Max (Min)blink
C. Parameter Setting
1 Basic Parameter
,
a) Basic Parameters description
Symbol
Description
Inty
Inty
Input Type
Dot
dot
Decimal point
PuL
PuL
Scale low
Puh
PuH
Scale high
Psb
PSb
Zero offset
Psbf
PSbF Range coefficient
Corf
CorF Temperature unit
Filt
FiLt
Digital filter
end
End
Exit
Note 1, for correcting the offset at zero: Display=measurement +PSb
This parameter only apply to temperature sensors
Note 2, for correcting the error at Max: Display=measurement x PSbF
Note 3, Digital filter. 0=no filter. 1 weak, 2, medium, 3 strong.
Note 4, These parameters define the scale boundary and resolution of
the display value. They do not apply to temperature sensors.
【
】
Table 1 Input type options
Symbol
Input type
t
TC, Type T
r
TC, Type R
j
TC, Type J
wre
TC, WRe3-WRe25
vdo
VDO water/oil
5
TC, Type S
k
TC, Type K
e
TC, Type E
p100
RTD, Pt100
cu50
RTD, Cu50
375r
0~375
"
>
"
75mv
0~75mV Current
30mv
0~30 mV
5v
0~5 V
1-5v
10v
10ma
0~10 mA
20ma
0~20 mA
4-20
4~20 mA
(TC, thermocouple sensor)
B)Basic Parameter setting See
2, Alarm Parameter
a) Alarm Parameters description
Symbol
Name
.
AH1
AL1
AH2
AH2
End
WWW.AUBERINS.COM
(Press
theninputcode0089toenter)
SET
Setting range
See Table 1
~ .
0000 0 000
~
-1999 9999
~
-1999 9999
~
-1000 1000
.
~ .
0 500 2 000
:
:
c
f
°C
~
0 3
Res.
Range
-200~400°C
1°C(F)
-50~1600°C
1°C(F)
-200~1200°C
1°C(F)
0~2300°C
1°C(F)
50~150°C
1°C(F)
-50~1600°C
1°C(F)
-200~1300°C
1°C(F)
-200~900°C
1°C(F)
-199.9~600.0°C
0.1°C(F)
-50.0~150.0°C
0.1°C(F)
Ω
Pressure
Display range
16 bitA/D
can be set in
1~5 V
-1999~9999
0~10 V
(
【
】
Fig3
(
Press
then input code 0001 to enter
SET
Description
Range
J1 pull in Value
-1999~9999
J1 drop out value
-199~9999
J2 pull in Value
-1999~9999
J2 drop out Value
-1999~9999
Exit
.
v1 7
Inintial
Note
k
00 00
.
4
00 01
.
4
03 15
.
4
0
1
.
1 000
2
f
°
F
0
3
Accy.
Impedance
0.3%
100K
0.3%
100K
0.2%
100K
0.2%
100K
0.3%
(0.2mA)
0.3%
100K
0.2%
100K
0.2%
100K
0.2%
(0.2mA)
0.5%
(0.2mA)
0.2%
(0.2mA)
100K
0.1%
0.1%
100K
0.1%
100K
0.1%
100K
0.1%
100K
Ω
0.3%
150
Ω
0.2%
150
Ω
0.2%
150
)
)
Initial
Note
900
5
800
900
800
P1/2