Anywire AnyWireASLINK BS-K5217-M30-1K Руководство по эксплуатации - Страница 2

Просмотреть онлайн или скачать pdf Руководство по эксплуатации для Аксессуары Anywire AnyWireASLINK BS-K5217-M30-1K. Anywire AnyWireASLINK BS-K5217-M30-1K 9 страниц. Aslink sensor

[AnyWireASLINK Terminal]
The AnyWireASLINK can employ a two-wire or four-wire terminal selectively depending
on the load current. If the load current is small, using a two-wire (non-isolated) terminal
allows for achieving simplified wiring without local power supply.
In the case of prioritizing the sites of concentrated loads and/or the number of
connections, hybridization with a four-wire (isolated) terminal, which supports local
power supply, is also possible.
Make sure to use a four-wire (isolated) terminal in the case of input and load driving
using an external power supply.
[System Configuration Example]
■Connection with a 2-wire (non-isolated) terminal only
Red:
DP
AnyWireASLINK
master
Black:
DN
*
24V DC
*
Make sure to use a
24V DC stabilized
Red: DP
power supply for the
power supply to be
connected.
Black: DN
*
When complying with
Red: DP
the UL Standard, make
sure to use a 24V DC
stabilized power supply
Black: DN
of "NEC Class 2
Output."
Red: DP
Black: DN
Red: DP
Black: DN
Dedicated flat cable
1.25mm
2
(2-wire)
2P link connector is
convenient for
branching.
The sum of the
portions of DP, DN is
the total line length.
Black: DN
Red: DP
AnyWireASLINK terminator
One terminator should be connected to the DP, DN
terminal farthest from the AnyWireASLINK master.
Connect it correctly so as not to set the wrong polarity.
■Relationship between the size and length of
the transmission line and the supply current (Table 1)
Supply current on the transmission line (DP, DN)
Size of
the transmission
Total length:
line (DP, DN)
50m or less
1.25mm
MAX 2A
2
0.75mm
MAX 1.2A
2
0.5mm
MAX 0.8A
2
- Refer to Table 1 so that the size and length of the transmission
CAUTION
line and the allowable supply current lie within an appropriate
range.
- Connect the same symbols (DP, DN) correctly between the AnyWireASLINK
master and each device.
- The branching length or branch number has no limitation.
- Include the length of the cable provided with the terminal in the "total line length."
- Connect the terminator BT0 (with polarity) on the transmission line terminal
farthest from the AnyWireASLINK master unit.
Red: DP
2 points
Black: DN
Red: DP
Retroreflective type
Black: DN
Independent use of
ASLINKAMP
Expansion of
ASLINKAMP
Expansion of
ASLINKAMP
Reflector
(optional)
Retroreflective type
Retroreflective type
Black: DN
The branching
Red: DP
has no limitation.
Red: DP
Total length: Over 50m,
Total length: Over 100m,
no longer than 100m
no longer than 200m
MAX 1A
MAX 0.5A
MAX 0.6A
MAX 0.3A
MAX 0.4A
MAX 0.2A
■Example of mixed installation with 2-wire (non-isolated) and
4-wire (isolated) terminals
AnyWireASLINK
master
General-purpose
power supply filter
*
24V DC
Dedicated flat cable
1.25mm
2
(4-wire)
4P link connector is
convenient for
branching.
Black: DN
2 points
The sum of the
portions of DP, DN is
the total line length.
24V DC
always use a 4-wire (isolated) terminal.
Otherwise, malfunction may be caused.
-BSK5217M**1K 2/9-
Red:
Red: DP
DP
2 points
Black:
Black: DN
DN
ASLINK filter
Red: DP
2 points
Black: DN
Red: DP
Black: DN
Red: DP
Black: DN
Red: DP
Black: DN
Red: DP
Black: DN
Red: DP
Black: DN
Retroreflective type
The branching
has no limitation.
Black:
Red: DP
*
DN
AnyWireASLINK terminator
One terminator should be connected to the DP, DN
terminal farthest from the AnyWireASLINK master.
Connect it correctly so as not to set the wrong polarity.
To connect loads (e.g. I/O ports) that are
CAUTION
controlled with a power supply other than the
one used for the AnyWireASLINK system,
8 points
Red: DP Black: DN
Retroreflective type
Independent use of
ASLINKAMP
Expansion of
ASLINKAMP
Expansion of
ASLINKAMP
Reflector
(optional)
Retroreflective type
8 points
Black: DN
Red: DP
Red: DP Black: DN
2 points