Apollo 45681-265 Руководство по установке - Страница 2
Просмотреть онлайн или скачать pdf Руководство по установке для Морское оборудование Apollo 45681-265. Apollo 45681-265 2 страницы. Intelligent base sounder
Technical data
Operating voltage
Sounder output
switch selectable 85 or 92dB(A)
SPL polar plot data is available in document
M04-002, available on request.
Current consumption at 24V DC
quiescent
switch-on surge
sounder operated at 85dB(A)
sounder operated at 92dB(A)
IP rating
DIL Switch
Black
To XP95 base
© Apollo Fire Detectors Limited J.Roughton 2003
Fig 1 Connecting diagram
17—28V DC
300μA
1.2mA for 1 sec
3.5mA
8.25mA
21C
1 2 3 4 5 6 7 8 9
OPEN
Terminal
block
– – + +
L1 L2
Red
www.acornfiresecurity.com
Address Address and Sound Output Setting
The address of the base sounder is set using seven segments of the nine-segment DIL switch
(Fig 2). Segments 1-7 of the switch are set to "1" or "0" (ON), using a small screwdriver or similar
tool. A complete list of address settings is shown below.
The eighth seg ment selects the sound output level, 85dB(A) or 92dB(A) (ON).
Master/slave setting
Sounders are factory set with the ninth segment of the DIL switch set to "0" (ON) — 'Master'.
Please see PIN sheet PP2136 for an explanation of this concept. Do not set sounders as slaves
without consulting this document.
DIL switch
setting
addr
1234567
1
1000000
2
0100000
3
1100000
4
0010000
5
1010000
6
0110000
7
1110000
8
0001000
9
1001000
10
0101000
51
1100110
52
0010110
53
1010110
54
0110110
55
1110110
56
0001110
57
1001110
58
0101110
59
1101110
60
0011110
101
1010011
102
0110011
103
1110011
104
0001011
105
1001011
Example of address and output setting
Address shown is 78, a sound out put of 85dB se lect ed and the sounder confi gured as a
master sounder.
Fig 2
www.acornfiresecurity.com
DIL switch
DIL switch
setting
setting
addr
1234567
addr
1234567
addr
11
1101000
21
1010100
12
0011000
22
0110100
13
1011000
23
1110100
14
0111000
24
0001100
15
1111000
25
1001100
16
0000100
26
0101100
17
1000100
27
1101100
18
0100100
28
0011100
19
1100100
29
1011100
20
0010100
30
0111100
61
1011110
71
1110001
62
0111110
72
0001001
63
1111110
73
1001001
64
0000001
74
0101001
65
1000001
75
1101001
66
0100001
76
0011001
67
1100001
77
1011001
68
0010001
78
0111001
69
1010001
79
1111001
70
0110001
80
0000101
106
0101011
111
1111011
116
107
1101011
112
0000111
117
108
0011011
113
1000111
118
109
1011011
114
0100111
119
110
0111011
115
1100111
120
Example:
Individual
Vol
Master/
Address 78 =
85
Slave
0
1
1
1
0
0
1
1 0
O
1
2
3
4
5
6
7
8
9
ON = 0
N
Individual Address
Vol
Master
© Apollo Fire Detectors Limited 2006-9/JDR/TP
DIL switch
DIL switch
setting
setting
1234567
addr
1234567
31
1111100
41
1001010
32
0000010
42
0101010
33
1000010
43
1101010
34
0100010
44
0011010
35
1100010
45
1011010
36
0010010
46
0111010
37
1010010
47
1111010
38
0110010
48
0000110
39
1110010
49
1000110
40
0001010
50
0100110
81
1000101
91
1101101
82
0100101
92
0011101
83
1100101
93
1011101
84
0010101
94
0111101
85
1010101
95
1111101
86
0110101
96
0000011
87
1110101
97
1000011
88
0001101
98
0100011
89
1001101
99
1100011
90
0101101
100
0010011
0010111
121
1001111
1010111
122
0101111
0110111
123
1101111
1110111
124
0011111
0001111
125
1011111
126
0111111
Switch