Automationdirect.com Productivity 1000 P1-04RTD Руководство

Просмотреть онлайн или скачать pdf Руководство для Системы ввода/вывода Automationdirect.com Productivity 1000 P1-04RTD. Automationdirect.com Productivity 1000 P1-04RTD 8 страниц. Analog input

Automationdirect.com Productivity 1000 P1-04RTD Руководство

RTD Input Specifications

Inputs Channels
Data Format
Max. Common Mode Voltage
Common Mode Rejection
Absolute Maximum Ratings
Internal Resolution
RTD Input Ranges
RTD Linearization
Excitation Current (all ranges)
Accuracy vs. Temperature
Warm-up Time
Maximum Inaccuracy*
Sample Duration
(Single channel update rate)
Filter Characteristics
All Channel Update Rate
Open Circuit Detection Time
Conversion Method
External DC Power Required
*NOTE: Excluding RTD error, including temperature drift
Sales 800-633-0405
4 Differential
Floating Point
5VDC
-100dB min. @ DC, -100db min. @ 50/60 Hz*
Fault Protected Inputs to ±50V
16-bit, ±0.1°C or °F
Pt100
-200°C/850°C (-328°F/1562°F)
Pt1000
-200°C/595°C (-328°F/1103°F)
JPt100
-100°C/450°C (-148°F/842°F)
10: Cu.
-200°C/260°C (-328°F/500°F)
25: Cu.
-200°C/260°C (-328°F/500°F)
120: Ni.
-80°C/260°C (-112°F/500°F)
Automatic
210µA
±10ppm per °C (maximum)
2 minutes for ±0.2% repeatability
±1°C maximum @ 16.7 Hz
±3°C maximum @ 470Hz
±5°C maximum on Cu10 & Cu25
Dependent on digital filter settings-
200ms @ 16.7 Hz, 90ms @ 470Hz
Digital Filter cutoff frequencies:
16.7 Hz, 470Hz
Single channel update rate times the number of
enabled channels
Burnout detect within 2s
Sigma-Delta
None
P1-04RTD Analog Input
P1-04RTD
The P1-04RTD Input Module provides four differential
channels for receiving RTD and resistance input
signals for use with the Productivity1000 system.
RTD Input Specifications . . . . . . . . . . . . . . . . . . . . . 1
General Specifications . . . . . . . . . . . . . . . . . . . . . . 2
Wiring Diagram and Schematic . . . . . . . . . . . . . . . . 3
Module Installation Procedure . . . . . . . . . . . . . . . . . 4
R1+
QR Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Wiring Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
R1-
Module Configuration . . . . . . . . . . . . . . . . . . . . . . . 5
R2+
Resistance Input Specifications . . . . . . . . . . . . . . . 6
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
R2-
Typical Application Example . . . . . . . . . . . . . . . . . . 7
Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
COM
R3+
R3-
R4+
R4-
RTD
INPUT
Warranty: Thirty-day money-back guarantee. Two-year limited
replacement (See www.productivity1000.com for details).
www.productivity1000.com
1000
1