Input Connections, Analog Sensors (VX12i)

Analog sensors o er a "variable" value such as a temperature, pressure, etc. The device's analog inputs are 12
bit and o er 4096 steps of resolution (1.22mV or 0.005mA.) Each input has a default range in "Voltage" mode
of 0-5Vdc, or if set with a jumper to a "Current" mode, a 0-20mA range.
Voltage Mode
Standard mode for 0-5Vdc analog sensors or discrete type sensors.
Current Mode
Mode for 0-20mA or 4-20mA type industrial analog sensors.
Note: Jumpers must be installed on the PCB for mA mode.
Analog Sensor
(Moisture Probe)
Bare (v-)
Red (v+)
Black (signal)
GND
GND
GND
GND