Galvin Engineering CliniMix Lead Safe 100.00.71.00 Установка изделия Manualline - Страница 7
Просмотреть онлайн или скачать pdf Установка изделия Manualline для Сантехническая продукция Galvin Engineering CliniMix Lead Safe 100.00.71.00. Galvin Engineering CliniMix Lead Safe 100.00.71.00 18 страниц. Hob mounted thermostatic progressive basin mixer - lever
st
Version 2.1, 31
July 2020 , 7 of 18
Restore the cold-water supply to the valve. After the mixed water temperature has stabilised note the outlet
temperature ensuring the outlet temperature has re-established. The time taken to stabilise the temperature
should not exceed the maximum time set out in the applicable standard or code of practice for each state.
Shut Down Test 2
With the mixer still set in full hot position and with both supplies turned on allow the flow to stabilise for at least
15 seconds and record the temperature. Quickly isolate the hot water supply to the valve.
The outlet flow should quickly reduce to be less than 0.4L/min following the isolation. The volume of mixed
water discharged for a period of between 5-35 seconds should be measured and should not exceed the
maximum volume set out in the applicable standard or code of practice for each state.
Restore the hot water supply to the valve and measure and record the outlet temperature after the mixed
water temperature has stabilised. The time taken to stabilise the temperature should not exceed the
maximum time set out in the applicable standard or code of practice for each state.
Ensure that all details of the Commissioning Report are completed, and a copy is kept with the installer and
owner of the premises.
The valve is now commissioned, and it can be used within the technical limits of operation.
7