Merlin GDP2
2.4
EM REMOTE (Remote emergency shut off buttons)
The terminal for remote emergency shut-off buttons is detailed on the
circuit board as [EM REMOTE].
These connections are linked out as a factory setting. Remote
emergency shut-off buttons should be volt free and wired to the Merlin
GDP2 using two-core cable.
2.5 HEAT SENSOR
The terminal for heat detectors is detailed as [HEAT SENSOR].
These connections are linked out as a factory setting.
Heat detectors should be volt free and wired to the Merlin GDP2 using two-
core cable.
2.6
FIRE PANEL
The terminal for fire alarms is detailed as [FIRE PANEL].
These connections are linked out as a factory setting.
Fire alarms should be volt free and wired to the Merlin GDP2 using two-
core cable.
2.8
SOUNDER/STROBE
The terminal for audible/visual alarms is detailed on the circuit board as
[SOUNDER/STROBE].
Sounder alarms should be wired using low voltage cable and wired to the
Merlin GDP2 using two-core cable.
This terminal has a 24VDC output.
Rev: 05 05-19
2.7
BMS OUT
Terminal connections are available on the circuit board for connections
to Building Management Systems etc.
Marked on the circuit board as [BMS OUT - N/O - COM - N/C] these are
volt free connections.