aguilera AE/SA-MC5 Техническое руководство

Просмотреть онлайн или скачать pdf Техническое руководство для Блок управления aguilera AE/SA-MC5. aguilera AE/SA-MC5 2 страницы. Algorithmic master modules

Disconnect a detector from the detector loop and check that the zone passes to a fault state.
Reconnect the detector. Check that the zone passes automatically to the idle state.
The modules that have not passed the operating tests should be replaced and repaired.
When the tests have been completed, reconnect the functions previously disabled, and notify the competent authority that
the fire detection system is again in service.
MAINTENANCE
The minimum maintenance recommended for a module consists of a visual inspection, as well as a periodic operating test.
For the operating test, follow the previously indicated procedure. (See the operating manual of the corresponding
algorithmic panel).
MODULE CODING
All algorithmic equipment must be coded with a number as corresponds to its personalization. The recording of the module
numbering can be carried out from:
1.
AE/SA-PRG manual address programmer. See the programmer's manual for their coding.
2.
Algorithmic Panel. See operating manual of the algorithmic panel for their coding.
Program a number between 1 and 125 as corresponds for their personalization. For the algorithmic system, the module
occupies a single position inside the loop, although the text and operation of the detector loop and of the supervised output
can be personalized independently.
The identification number of the unit, as well as the operation pilot, is stored in EEPROM memory.
Before connecting the module to the algorithmic loop, verify the coding is correct.
INHIBITION OF FLASHING OF THE OPERATION PILOT
The operation pilot mode can be modified when carrying out the module programming process.
TECHNICAL CHARACTERISTICS
Power supply voltage:
18 ~27 V (AE/SA-CTL Algorithmic loop card).
Consumption when idle:
1 mA (auxiliary feed 17 mA)
Consumption in alarm state:
Modules AE/SA-M and AE/SA-MC5: 1.3 mA (auxiliary feed 44 mA)
Module AE/SA-MDL: 1.3 mA (auxiliary feed 90 mA)
Algorithmic loop wiring
2-wire. Recommended cross-section 1.5 mm
Removable jacks for all connections
Supervised output:
+24 Vdc
Relay characteristics:
Maximum resistive load = 1 A / 30 Vdc - 0.5 A / 125 Vac
Maximum switching voltage = 125 Vdc - 125 Vac
Maximum switching power = 30 W - 125 VA
Temperature range:
0º - +50º C (ambient temperature)
Humidity range:
Relative humidity 10% - 90% without condensation.
Casing material:
ABS
Luminous indicator:
Operation pilot:
Activation:
Size:
105 x 82 x 25 mm
Fastening:
4 holes, diam. 3.5 mm
Weight:
100g.
Ae-man-823-0.0 v1.1
HEADQUARTER OFFICE & FACTORY: C/ Julián Camarillo, 26 28037 – MADRID (SPAIN)
Telf.: +34 91 754 55 11 Fax.: +34 91 754 50 98 www.aguileraelectronica.es
2
red flash (can be inhibited).
red intermittent
TECHNICAL MANUAL
ALGORITHMIC MASTER MODULES
MASTER MODULES AE/SA-M
SERIES C5 DETECTOR MODULE: AE/SA-MC5
BEAM SMOKE DETECTOR MODULE: AE/SA-MDL
Units with microprocessor designed to be used with the algorithmic fire alarm panels of AGUILERA ELECTRONICA.
They include:
A conventional detection loop that can be, according to the model:
AE/SA-M Conventional detectors or manual call points loop.
AE/SA-MC5: Conventional detectors loop of C5 SERIES of Aguilera.
AE/SA-MDL: Single Beam smoke detector loop.
One supervised 24Vdc relay output, with end of line resistance.
These modules require an auxiliary power supply for operation.
The detection loop and the output are individually personalized in the Algorithmic Panel with the name of the location
and the operation performed. Its operation is independent.
They include:
Operation pilot: It indicates it is operating correctly, giving red-colored flashes through the status LED. The
flashing frequency depends on whether the equipment in idle or not. If the flashing were annoying in particular
cases, it can be inhibited individually.
Removable jacks, to facilitate connection in the field.
The circuit's protective case leaves the status LED of the unit visible.
Individual identification: Each module is identified individually with a single number inside the installation loop.
This number is stored in EEPROM memory whereby it is kept even though the module is without power for a
long period.
Ae-man-823-0.0 v1.1
HEADQUARTER OFFICE & FACTORY: C/ Julián Camarillo, 26 28037 – MADRID (SPAIN)
Telf.: +34 91 754 55 11 Fax.: +34 91 754 50 98 www.aguileraelectronica.es
TECHNICAL MANUAL