Ratings, fuses and typical power cable sizes
ACH580-
Nominal ratings
01-...
Input
Output
current
current
I
I
1
2
A
A
U
= 200...240 V, P
at U
= 3-phase 208/230 V, 60 Hz
1
n
n
04A6-2
4.6
4.6
06A6-2
6.6
6.6
07A5-2
7.5
7.5
10A6-2
10.6
10.6
017A-2
16.7
16.7
024A-2
24.2
24.2
031A-2
30.8
30.8
046A-2
46.2
46.2
059A-2
59.4
59.4
075A-2
74.8
74.8
088A-2
88.0
88.0
114A-2
114
114
143A-2
143
143
169A-2
169
169
211A-2
211
211
273A-2
273
273
U
= 440...480 V, P
at U
= 3-phase 460 V, 60 Hz
1
n
n
02A1-4
2.1
2.1
03A0-4
3.0
3.0
03A5-4
3.5
3.5
04A8-4
4.8
4.8
06A0-4
6.0
6.0
07A6-4
7.6
7.6
012A-4
12.0
12.0
014A-4
14.0
14.0
023A-4
23.0
23.0
027A-4
27.0
27.0
034A-4
34.0
34.0
044A-4
44.0
44.0
052A-4
52
52
065A-4
62
62
077A-4
77
77
078A-4
78
78
096A-4
106
106
124A-4
124
124
156A-4
156
156
180A-4
180
180
240A-4
240
240
260A-4
260
260
302A-4
302
302
361A-4
361
361
414A-4
414
414
U
= 500...600 V, P
at U
= 3-phase 575 V, 60 Hz
1
n
n
02A7-6
2.7
2.7
03A9-6
3.9
3.9
06A1-6
6.1
6.1
09A0-6
9.0
9.0
011A-6
11.0
11.0
017A-6
17.0
17.0
022A-6
22
22
027A-6
27
27
032A-6
32
32
041A-6
41
41
052A-6
52
52
062A-6
62
62
077A-6
77
77
099A-6
99
99
125A-6
125
125
Description
The Safe torque off circuit 2 is broken.
Motor
gG fuse
1)
power
(IEC 60269)
P
n
ABB type
kW
hp
0.75
1.0
OFAF000H25
1.1
1.5
OFAF000H25
1.5
2.0
OFAF000H25
3.0
3.0
OFAF000H25
4.0
5.0
OFAF000H25
5.5
7.5
OFAF000H40
7.5
10.0
OFAF000H40
11.0
15.0
OFAF000H63
15
20
OFAF000H63
15
25
-
22
30
OFAF00H125
30
40
OFAF00H125
37
50
OFAF0H200
45
60
OFAF0H250
55
75
OFAF1H315
75
100
OFAF2H400
0.75
1.0
OFAF000H4
1.1
1.5
OFAF000H6
1.5
2.0
OFAF000H6
2.2
3.0
OFAF000H10
3.0
3.0
OFAF000H10
4.0
5.0
OFAF000H16
5.5
7.5
OFAF000H16
7.5
10.0
OFAF000H25
11.0
15.0
OFAF000H32
15.0
20.0
OFAF000H40
18.5
25.0
OFAF000H50
22.0
30.0
OFAF000H63
30
40
OFAF000H80
37
50
OFAF000H100
-
60
-
45
60
OFAF000H100
55
75
OFAF00H125
75
100
OFAF00H160
90
125
OFAF0H250
110
150
OFAF1H315
132
200
OFAF1H355
160
200
OFAF2H425
-
250
-
200
300
OFAF2H500
250
350
OFAF3H630
1.5
2.0
-
2.2
3.0
-
4.0
5.0
-
5.5
7.5
-
7.5
10.0
-
11.0
15.0
-
15.0
20.0
-
18.5
25.0
-
22.0
30.0
-
30
40
-
37
50
-
45
60
-
55
75
-
75
100
-
90
125
-
3)
Fuses
uR/aR
UL class
2)4)
5)6)7)
fuse
T
(DIN 43620)
Bussmann type
170M1563
JJS-15
170M1563
JJS-15
170M1563
JJS-15
170M1563
JJS-15
170M1563
JJS-30
170M1565
JJS-40
170M1565
JJS-40
170M1566
JJS-80
170M1566
JJS-80
-
JJS-100
170M3815
JJS-150
170M3815
JJS-150
170M3817
JJS-200
170M5809
JJS-250
170M5810
JJS-300
170M6810
JJS-400
170M1561
JJS-15
170M1561
JJS-15
170M1561
JJS-15
170M1561
JJS-15
170M1561
JJS-15
170M1561
JJS-15
170M1561
JJS-15
170M1563
JJS-30
170M1563
JJS-30
170M1565
JJS-40
170M1565
JJS-60
170M1566
JJS-60
170M1567
JJS-80
170M1568
JJS-100
-
JJS-100
170M1569
JJS-110
170M3817
JJS-150
170M3817
JJS-200
170M5809
JJS-225
170M5810
JJS-300
170M5812
JJS-350
170M6812D
JJS-400
-
JJS-500
170M6814D
JJS-500
170M8554D
JJS-600
-
JJS-15
-
JJS-15
-
JJS-15
-
JJS-15
-
JJS-15
-
JJS-30
-
JJS-40
-
JJS-40
-
JJS-40
-
JJS-100
-
JJS-100
-
JJS-100
-
JJS-100
-
JJS-150
-
JJS-200
Typical power cable sizes,
Cu
2 8)
9)
mm
AWG
3×1.5 + 1.5
14
3×1.5 + 1.5
14
3×1.5 + 1.5
14
3×1.5 + 1.5
14
3×2.5 + 2.5
10
3×4.0 + 4.0
8
3×6.0 + 6.0
8
3×10 + 10
6
3×10 + 10
4
-
3
3×35 + 16
2
3×50 + 25
1/0
3×70 + 35
3/0
3×95 + 50
4/0
3×120 + 70
300 MCM
2×(3×70 + 35)
500 MCM
or 2×2/0
3×1.5 + 1.5
14
3×1.5 + 1.5
14
3×1.5 + 1.5
14
3×1.5 + 1.5
14
3×1.5 + 1.5
14
3×2.5 + 2.5
14
3×2.5 + 2.5
14
3×2.5 + 2.5
12
3×6 + 6
10
3×10 + 10
8
3×10 + 10
8
3×10 + 10
6
3×25 + 16
4
3×35 + 16
4
-
3
3×50 + 25
3
3×70 + 35
1/0
3×95 + 50
2/0
3×120 + 70
3/0
3×150 + 70
4/0
2×(3×70+35)
2×1/0 or
350 MCM
2×(3×95+50)
2×2/0
-
2×3/0
2×(3×120+70)
2×4/0
2×(3×150+70)
2×300
MCM
-
14
-
14
-
14
-
14
-
14
-
10
-
10
-
8
-
8
-
6
-
4
-
2
-
2
-
1/0
-
3/0
13
Frame
size
R1
R1
R1
R1
R1
R2
R2
R3
R3
R4
R5
R5
R6
R7
R7
R8
R1
R1
R1
R1
R1
R1
R1
R2
R2
R3
R3
R3
R4
R4
R4
R5
R5
R6
R7
R7
R8
R8
R9
R9
R9
R2
R2
R2
R2
R2
R2
R3
R3
R3
R5
R5
R5
R5
R7
R7