Service Support Spirit
ARC ON Light
Solution: Keep pressing 【ARCING TEST】Button on the THC panel, If【ARCON】
light is on , At the same time, there is has an output arcing signal on the THC board.
--Check ARCING Signal ,Keep pressing 【ARCING TEST】Button, At the same time, Use
a multimeter to check.
If there is a ON between ARCSTART_1 and ARCSTART_2. Prove that the THC is working;
If there is a OFF between ARCSTART_1 and ARCSTART_2. Prove that the THC is Bad ,Please
change new THC;
Test CNC ARCING signal:
Keep pressing 【Piercing】Button on the CNC panel, If 【 ARCON】light is on , At the same
time, there is has an output arcing signal on the THC board.
--Check ARCING Signal ,Keep pressing 【Piercing】Button, At the same time, Use a
multimeter to check.
If there is a ON between ARCSTART_1 and ARCSTART_2. Prove that the CNC is working;
If there is a OFF between ARCSTART_1 and ARCSTART_2. Prove that the CNC is Bad ,Please
contact ARCBRO;