APOGEE Heat Pump Controller—Multi Stage Owner's Manual
Descriptor
Address
CLG OUTPUT
61
OA DMPR POS
62
CLG P GAIN
63
CLG l GAIN
64
CLG D GAIN
65
CLG BIAS
66
HTG P GAIN
67
HTG l GAIN
68
HTG D GAIN
69
HTG BIAS
70
ROOM P GAIN
71
ROOM I GAIN
72
ROOM D GAIN
73
ROOM BIAS
74
CMP MIN OFF
75
CMP MlN ON
76
AUX LOOPOUT
77
28
Application
2281, 2283,
If the cooling control device is not DX, then the value of this
2284, 2286,
point indicates the position of the cooling actuator. If DX cooling
2287
is used, then the value of this point determines whether DX is
ON or OFF.
Valid values: 0 to 100%
2281, 2283,
Indicates the position of the outdoor air damper actuator.
2284, 2286,
2287
2281, 2283,
The proportional gain value for the cooling temperature control
2284, 2286,
loop.
2287
2281, 2283,
The integral gain value for the cooling temperature control loop.
2284, 2286,
2287
2281, 2283,
The derivative gain value for the cooling temperature control
2284, 2286,
loop.
2287
2281, 2283,
The biasing of the cooling temperature control loop. Refer to
2284, 2286,
CLG LOOPOUT (Point79).
2287
2281, 2283,
The proportional gain value for the heating temperature control
2284, 2286,
loop.
2287
2281, 2283,
The integral gain value for the heating temperature control loop.
2284, 2286,
2287
2281, 2283,
The derivative gain value for the heating temperature control
2284, 2286,
loop.
2287
2281, 2283,
The biasing of the heating temperature control loop. Refer to
2284, 2286,
HTG LOOPOUT (Point 80).
2287
2281, 2284
The proportional gain value for the room control loop.
2281, 2284
The integral gain value for the room control loop.
2281, 2284
The derivative gain value for the room control loop.
2281, 2284
The biasing of the room loop output point, DISCH STPT (Point
93).
2284, 2286,
The minimum time, in minutes, which the unit ventilator's
2287
compressor will remain OFF before turning ON again.
Valid input: 0 to 255 minutes
2284, 2286,
The minimum time, in minutes, which the unit ventilator's
2287
compressor will remain ON before turning OFF again.
Valid input: 0 - 255 minutes
2281, 2284
The control loop output value that is used to determine AUX
OUTPUT (Point 55).
Description
Siemens Building Technologies, Inc.