Actulux SVM EI 24V-8A Инструкция по установке - Страница 10
Просмотреть онлайн или скачать pdf Инструкция по установке для Панель управления Actulux SVM EI 24V-8A. Actulux SVM EI 24V-8A 13 страниц. Control panel for fire ventilation
Control for Fire and Comfort Ventilation Type SVM EI 24V-5A / SVM EI 24V-8A
Lock-Out Mode SLAVE
Slaves are connected to Smoke Vents on each floor.
DIP11 = ON
DIP12 = ON
When Slave Panel receives an alarm signal from Manual control Point or Smoke Detector:
- it enters Alarm, sets it's motor output in open direction and transmit Fire on the bus.
- the Master enters Alarm (Flashes 1 Hz with Alarm led) and sets it's motor output in open direction.
- the other Slaves enter lockout (Flashes 10 Hz with Alarm led) and set it's motor output in close direction
the lockout slave's can't enter alarm mode from manual control point or smoke detector, before reset has
been executed.
Fireman's Priority Switch:
Slaves can have a local Fireman's Priority switch to override the lock-out mode.
The Fireman's Override Switch will be able to control the slave panel whatever the alarm condition.
Pressing Open / Close buttons on the Fireman's Priority Switch at the same time:
- reset is executed.
- the blue led will flash for 5 seconds.
- Open / Close buttons are disabled during this.
NOTE - A Slave unit in lockout mode will not respond to any inputs.
The only way of controlling the Slave unit in lock-out mode, is by using a Fireman's Priority Switch.
ALARM ON ONE OF THE SLAVES
SLAVE EVENT
SMOKE
FIRE MODE
Manual Control Point (MCP)
MCP (BVT)
FIRE MODE
MASTER
SLAVE
MCP
SMOKE
MCP
SMOKE
Smoke Detector
MASTER
SLAVE
MCP
SMOKE
MCP
SMOKE
Only mandatory
in UK!
27-02-2018
MASTER
ALL OTHER SLAVES
FIRE mode
Lock-Out mode
FIRE mode
Lock-Out mode
LOCK-OUT
LOCK-OUT
SLAVE
SLAVE
MCP
SMOKE
MCP
SMOKE
LOCK-OUT
LOCK-OUT
SLAVE
SLAVE
MCP
SMOKE
MCP
SMOKE
18
Control for Fire and Comfort Ventilation Type SVM EI 24V-5A / SVM EI 24V-8A
Lock-Out Mode MASTER
Master is connected to the Smoke Vent.
DIP11 = ON
DIP12 = ON
When Master Panel receives an alarm signal from Manual control Point or Smoke Detector:
Only Master panel enters alarm mode sets it's motor output in open direction
Fireman's Priority Switch:
The Master can have a Fireman's Priority Switch installed to overrule alarm mode.
The Fireman's Override Switch will be able to control the panel whatever the alarm condition.
Pressing Open / Close buttons on the Fireman's Priority Switch at the same time:
- reset is executed.
- the blue led will flash for 5 seconds.
- Open / Close buttons are disabled during this.
ALARM ON MASTER INPUT
MASTER EVENT
SMOKE
FIRE MODE
Manual Control Point (MCP)
MCP (BVT)
FIRE MODE
MASTER
SLAVE
MCP
SMOKE
MCP
SMOKE
Smoke Detector
LOCK-OUT
MASTER
SLAVE
MCP
SMOKE
MCP
SMOKE
Only mandatory
in UK!
27-02-2018
ALL SLAVES
-
Lock-Out mode
-
FIRE mode
SLAVE
SLAVE
MCP
SMOKE
MCP
SMOKE
LOCK-OUT
LOCK-OUT
SLAVE
SLAVE
MCP
SMOKE
MCP
SMOKE
19