Cisco ASR 5000 Руководство по установке - Страница 13

Просмотреть онлайн или скачать pdf Руководство по установке для Шлюз Cisco ASR 5000. Cisco ASR 5000 18 страниц. Applying power and verifying the installation
Также для Cisco ASR 5000: Руководство по установке (33 страниц), Процедура установки (8 страниц), Руководство по установке (37 страниц)

Cisco ASR 5000 Руководство по установке
Chassis Installation
There are two sets of grounding terminals located at the lower-rear of the chassis. The following figure and
the table that follows show the location of these terminals and provide specifications for the appropriate lug
and cable size.
Figure 3: Chassis Ground Terminals
Table 2: Terminal and Cable specifications
Item
1
2
Description
Ground Terminal:
2-hole lug (0.186-inch posts, spaced 0.630-inch on center).
The method of connection is: chassis - lug - flat washer - nut (3/8-inch). The nut(s) must be torqued
to 50 in-lb (5.65 N-m).
Ground Cable:
Cable length: Not more than 70 feet (21.336 meters) one way.
Cable size: 6 AWG (minimum), stranded copper.
Grounding the Chassis
ASR 5000 Installation Guide
13