Ariston GENUS 27 RFFI SYSTEM Руководство по установке - Страница 11

Просмотреть онлайн или скачать pdf Руководство по установке для Котел Ariston GENUS 27 RFFI SYSTEM. Ariston GENUS 27 RFFI SYSTEM 48 страниц. Type c boilers
Также для Ariston GENUS 27 RFFI SYSTEM: Руководство по установке (32 страниц)

Ariston GENUS 27 RFFI SYSTEM Руководство по установке
BC
F
D
J
HI
Fig. 2.6
Ø 60/100 mm
017A
Fig. 2.7
B004
A suitable terminal guard is available from:
TOWER FLUE COMPONENTS
Morley Road
Tonbridge
Kent TN9 1RA
The minimum acceptable spacing from the terminal to obstructions and ventila-
tion openings are specified in Fig. 2.6
F
G
A
E
K
L
G
The boiler is designed to be connected to a coaxial flue discharge system.
TERMINAL POSITION
A - Directly below an open window or other opening
B - Below gutters, solid pipes or drain pipes
C - Below eaves
016A
D - Below balconies or car-port roof
E - From vertical drain pipes and soil pipes
F - From internal or external corners
G - Above ground or below balcony level
H - From a surface facing a terminal
I - From a terminal facing a terminal
J - From an opening in the car port
(e.g. door, window) into dwelling
K - Vertically from a terminal in the same wall
L - Horizontally from a terminal in the same wall
mm
300
75
200
200
75
300
300
600
1200
1200
1500
300
018A
11