AERMEC DUALJET 20 Руководство по установке - Страница 12
Просмотреть онлайн или скачать pdf Руководство по установке для Кондиционер AERMEC DUALJET 20. AERMEC DUALJET 20 17 страниц. Dualjet series. controlled outlet fan coil

inside of the cover of the box.
• WARNING: Earth the installation.
• It is obligatory to connect the casing of
the fan coil unit to the earthing.
• It is mandatory to tighten the screw
that fixes the thermostat box to the side
of the fan coil unit as this provides the
earthing of the whole installation.
• The fan coil unit is a product that can
only be installed internally.
• The fan coil unit must be installed
in such a position that the air can be
INSTALLATION OF THE UNIT
• To install the unit proceed as
• Remove the casing by unscrewing the
screw.
• For wall mounting use expansion plugs
(not provided) as shown in the diagram.
• Carry out the hydraulic
connections.
The position and diameters of the
hydraulic connections are shown in the
dimensional data.
To avoid condensate drips during cool-
ing operation it is recommended to
properly insulate the water piping or
to install the appropriate auxiliary con-
densate tray, available as an accessory.
The condensate drain system must be
appropriately sized and the piping
positioned in such a way to maintain
a slope (min. 1%). To avoid unpleasant
smells a trap is recommended if the
condensate is connected to the sewage
system.
• Carry out the electrical connections as
detailed in the wiring schematics and
the chapter dedicated to the electronic
thermostat connections.
• Replace the casing, not forgetting to
connect the ambient sensor and micro-
switch.
distributed throughout the room and
that there are no obstacles (curtains or
objects) to the passage of the air from
the intake and discharge.
• The fan coil unit must be installed in
such a way as to make easy ordinary
maintenance (filter cleaning) and spe-
cial maintenance, as well as the access
to the air vent valve on the side of the
frame (connections side).
follows:
IDJULJ 1207 - 6339500_00
25