INSTALLATION, OPERATING, AND MAINTENANCE INSTRUCTIONS
The following is intended to provide the basic instructions for installation, operation and maintenance of the
StreamMaster electric monitor, and to assist in attaining the best possible performance from the unit. Read
and understand these operating instructions before use.
TOOLS REQUIRED
• Utility Knife
• Medium Phillips screwdriver
• Small Phillips screwdriver
• Electrician's pliers (multipurpose, stripping and crimping)
PRODUCT RATINGS
Maximum Motor Current Draw:
12 volt versions
24 volt versions
Normal Operating Current: (Depending on operating conditions–pressure, flow, etc.)
12 volt versions
24 volt versions
Minimum Voltage: (Truck engine must be operating for proper voltage requirement.)
All 12 volt motors: 11.5 volts while operating
All 24 volt motors: 23 volts while operating
Mass: 39 lbs. (17.7 kg)
Maximum Flow: 2000 gpm (7600 lpm)
Maximum Pressure: 200 psi (14 bar)
Noise Emission: 95 DL @ 1m with maximum flow
PRODUCT WARNINGS
L
!
WARNING: Charge the unit slowly. Rapid charging may cause a pressure surge that has the potential to
cause an injury, or damage the monitor.
L
!
WARNING: DO NOT stow or deploy the StreamMaster monitor while flowing. Pressing the stow or
deploy buttons causes the nozzle to move automatically and the water stream may cause
damage to equipment or injury to personnel.
L
!
WARNING: Aim the unit in a safe direction before pumping water through it. (i.e. Away from power lines)
STYLE 3578 STREAMMASTER™
(
Version Available)
• Medium flat screwdriver
• Small flat screwdriver
• 1/2 inch hex head wrench
14.0 amps each for elevation and rotation motors
3.0 amps for nozzle pattern motor
7.5 amps each for elevation and rotation motors
1.5 amps for nozzle pattern motor
3.0 to 10.0 amps each for elevation and rotation
0.7 amps for nozzle pattern motor
2 - 5 amps each for elevation and rotation motors
0.4 amps for nozzle pattern motor