Indicators and Controls
1
LCD Display
power
voice alarm
2
LEDs
system fault
fault
SELECT
BACK
DEFAULT
3
Keys
FAULT ACCEPT
FAULT CLEAR
AUDIO MON
LAMP TEST
4
Rotary Encoder
5
Loudspeaker
VAR8(EN54) and Variants – Installation Guide
2 x 40 character backlit alphanumeric display.
Used to display control menu, faults, overall system status, and
configuration data.
green
Lit if the unit is receiving DC power.
red
Lit to indicate that a voice alarm condition is present.
Lit to indicate that a system fault has been detected in the PA/VA
system. This requires immediate action as part(s) of the system used
for emergency functions may have been affected. A system fault will
always cause the 'fault' LED to be lit as well.
A system fault is triggered by a failure of any processor or memory,
yellow
critical to the Voice Alarm system, including those of the VAR8(EN54)
itself. A communication fault between the VAR8(EN54) and any
equipment or device that has been configured at the VAR8(EN54) and
that is critical to Voice Alarm functions will also trigger a system
fault.
Lit to indicate that the unit has detected a fault.
yellow
Flashes if a fault has not yet been accepted.
The left and right arrow keys move the item selection in the direction
selected, to the next item in the menu. The selected item is indicated
by [brackets] around the selection.
The up and down arrow keys toggle a selection, or increment a
number, or a letter of the alphabet when editing.
The rotary encoder acts in the same manner as these keys, and
enables faster editing.
Press after selecting an item to confirm the selection.
Press after selecting an item to cancel the selection.
If pressed repeatedly, this returns the display to the top-level menu.
Press to clear previously configured text strings quickly during
system configuration, or to return fields to their default values.
Accepts all current faults, steadies the flashing fault LED indication,
and turns off the audible alarm until a new fault condition occurs.
Clears all faults and sets all connected equipment to the 'no faults'
state, which also cancels any amplifier changeovers in effect. Any
persistent faults will be reported again on the next monitoring cycle.
Selects Audio Monitor sub-menu on the LCD display.
Tests all indicators on the VAR8(EN54) and on all connected
mainframe and amplifier units. The sounder and the LCD display are
also tested. The display shows 'LAMP + LCD + SOUNDER TEST', and
then solid black characters. The menu locks for the entire duration
of the test. This function is also available from the 'Tests' menu.
Multi-function:
An alternative for the
and decrement of menu items.
During Audio Monitoring it also acts as a volume control.
Dual function: Alarm Sounder and Audio Monitor.