ANDELI AJR3-1005 Kullanım Kılavuzu - Sayfa 11

Kontrolör ANDELI AJR3-1005 için çevrimiçi göz atın veya pdf Kullanım Kılavuzu indirin. ANDELI AJR3-1005 15 sayfaları.

10. Protection operation
10-1 The list for protection operation
When the soft starter occurs abnormity, the protection function runs, it trips immediately,
LED displays alarming name and concerned content, please refer to table 10-1-1.
Table 10-1-1
Panel display
Alarming name
The faults like over-voltage, under-voltage, or overheat, instantaneous
The fault has
stop terminal opening circuit has been removed, then, turn on the lamp,
been removed
press YES key to start the motor.
External instantaneo-
Check if 07 and 10 terminals are connected, and the NC contact are
us-stop
connected with other protective equipment or not.
terminal opens circuit
The starting is too frequently, or the power of motor isn't fitted with
Soft starter is over heat
that of soft starter.
The starting parameter is set improperly, or the load is too heavy, the
Over long starting
power capacity is not enough.
Check the power for 3-phase, make sure that by-pass contactor isn't
Input open-phase
clamped in the closing position, the controllable silicon isn't short
circuit, KG wire is connected well.
Examine output circuit and connecting wire of motor, make sure that
Output open-phase
by-pass contactor isn't clamped in the closing position, the controllable
silicon isn't short circuit, KG wire is connected well.
Three-phase unbalance
Check if input three-phase power and load motor are normal or not.
Check if the load is too heavy or not, or the power of motor isn't fitted
Start over-current
with that of soft starter.
Run over-load protection
Check if the load is too heavy or not, or the P7 parameter is set wrong.
Check input supply voltage, or P9 parameter is set wrong.
Too low supply voltage
Check input supply voltage, or PA parameter is set wrong.
Too high supply voltage
The set parameter is error
Amend the setting or press
Check the load or motor, and the controllable silicon is short circuit
Load short-circuit
or load is too large.
Automatic restart,
Check the external control starting and stopping terminal is connected
the connection is
with 2-wire controlling mode.
error
The connection of
When the external control mode is permitted, the external control
external stopping
stopping terminal is in the open-circuit state, so it can't start the
terminal is error
motor.
Some faults is related, for example, report that
over current or load short-circuit, therefore, when check the fault, please consider compr-
ehensively, to judge the faults accurately.
Notice:
When soft starter starts motor successfully, the indication lamp for running in the middle
of panel lightens, it says that the it runs at the bypass, if the bypass contactor can't absorb,
it will cause the motor stops running, thus, you shall check the bypass contactor and con-
nection.
Operation content and treatment
确认
key to start and recover the factory value.
YES
soft starter is over heat, starting
-17-

11. Fault diagnosis

11-1 Problem and countermeasure
Abnormity
Content checked
The wiring
Weather the power wire
is connected to input the
terminal or not.
(1L1, 3L2, 5L3)
The motor
Weather bypass contactor
can't run
works or not, and 01, 02
terminal has no signal or not.
Weather the keyboard is
abnormal to display or not.
Weather the motor is locked
or not, (Weather the load is
too heavy or not).
Weather the keyboard has
The
displayed or not.
keyboard
Weather 07, 10 terminals
can't start
open circuit or not, PD
setting is correct or not.
External
Weather PD is set at ext-
control
ernal controlling or not.
can't start
Although
the motor
Weather the load is too
rotates, the
heavy or not.
speed is not
changed.
The load is too heavy, the
The starting
code hasn't been set, wea-
time is too
ther the spec of motor is
long.
correct or not.
The load is light
The starting
The starting time is too
time is short
short
It stops
suddenly
Check the external input
during
terminal
running.
Countermeasure
Please give the correct wiring
Switch on power
Cut off the power, then switch on
Check the connection situation of bypass contactor.
Check the connection situation of coil of bypass
contactor.
Please read P17 Protection operation list
"
"
Clear away the locking of motor (Reduce the load)
No: Weather the power opens phase or not, check
the inlet power.
Yes: 10 and 07, 08 open circuit, check external con-
nection of terminal, please set the PD code correctly.
Terminal 10 and 07, 08 opens circuit, check the ext-
ernal connection of terminal, please set the FD code
correctly, check if it is in the external control poison
or not
Please reduce the load
Add the initial voltage or starting current
Please reduce the load
Please set P0 (Initial voltage), P6 (Starting current),
P1(Starting time)
Please check the specification and nameplate
When the load is light, the starting time is often less
than setting value, the starting is normal, set the sta-
ring time of P1( the current mode is unavailable).
Check connection of 07, 10 terminals fails or not.
If the external protector is equipped with, please
check NC contact operates or not
Check the connection of external stop button fails
or not.
-18-