Atkinson Electronics GSCM Çalıştırma ve Kurulum Talimatları - Sayfa 11

Kontrol Ünitesi Atkinson Electronics GSCM için çevrimiçi göz atın veya pdf Çalıştırma ve Kurulum Talimatları indirin. Atkinson Electronics GSCM 16 sayfaları. Generator start control module
Ayrıca Atkinson Electronics GSCM için: Manuel (16 sayfalar)

Atkinson Electronics GSCM Çalıştırma ve Kurulum Talimatları
GENERATOR START CONTROL MODULE
GSCM
APPLICATION 4 - DIESEL GENERATORS
The diesel generator is started by the GSCM in either automatic or manual mode. A field installed relay that will handle the glow
plug current is needed if not already installed on the engine. A fuel control solenoid is connected to the K3 (ignition) relay
terminals. A decompression solenoid furnished with the generator must be wired to K4 (shutdown) relay to energize on shutdown.
APPLICATION 5 - AUTOMATIC GENERATOR POWERED AC PUMP
In this application the GSCM is connected to a pressure or level switch into the battery sense terminals. See Section-3:9 for
making the appropriate cut-in and cut-out adjustments. The cut-in and cut-out adjustments must be set at the maximum for the
switched input auto start mode to operate (see Sections 3:9 & 4:9). The K5 (load) relay energizes the pump contactor.
ATKINSON ELECTRONICS, INC.
REV 8/06
Web Site: www.atkinsonelectronics.com
Distributed by: