Mounting the Device
You can mount the device on a desktop using the four anti-slide bumpers (supplied), which you need to stick on
the grooves located on the underside of the device.
Alternatively, you can mount the device in a standard 19-inch rack, using one of the following methods:
Attaching the device to the rack posts using the pre-attached front-mounting brackets. When using this
method, it is highly recommended that the device be placed on a pre-installed rack shelf (not supplied)
for additional support.
Attaching the device to the rack posts using the pre-attached front-mounting brackets and rear-
mounting brackets (separate orderable item).
Cabling the Device to Power
1. GROUNDING:
Ground (earth) the device by connecting an electrically earthed strap of 16-AWG
(minimum) wire to the device's grounding screw located on the rear panel, using the supplied washer.
Connect the other end of the strap to protective earthing. This should be in accordance with
regulations enforced in the country of installation. The grounding screw must be connected to the
equipotential grounding bus bar located in the Telecommunication rack, using a wire of 6 mm
wire. This line must be connected to the equipotential bus bar of the electrical circuit board located in
the Telecommunication room, using a stranded cable with surface area of 25 mm
cable must be as short as possible (no longer than 3 meters).
2.
Connect the line socket of the AC power cord (supplied) to the device's AC power inlet (left) located on
the rear panel. Connect the plug at the other end of the AC power cord to a standard electrical outlet.
4 |
P a g e
2
surface
2
. The length of this