Apollo Smoke Detector XP95 Kurulum Kılavuzu - Sayfa 2

Güvenlik Sensörleri Apollo Smoke Detector XP95 için çevrimiçi göz atın veya pdf Kurulum Kılavuzu indirin. Apollo Smoke Detector XP95 2 sayfaları. Input/output unit
Ayrıca Apollo Smoke Detector XP95 için: Kurulum ve Bakım Kılavuzu (4 sayfalar), Kurulum Kılavuzları (2 sayfalar), Kurulum Kılavuzu (2 sayfalar), Hızlı Başlangıç Kılavuzu (2 sayfalar), Hızlı Başlangıç Kılavuzu (5 sayfalar), Kurulum Kılavuzu (18 sayfalar), Kurulum Kılavuzu (2 sayfalar)

Apollo Smoke Detector XP95 Kurulum Kılavuzu
Wiring Details
All wiring terminals will accept solid or stranded cables up to 2.5mm²
L1 (–ve)*
L2 (+ve)*
* L1 and L2 are polarity insensitive, but, for the sake of consistency, it is recommended that L1 be kept negative
XP95 LOOP
Currrent consumption, max @ 24V
switch-on surge, max 100 ms
quiescent
relay operated
For a full technical specification of the Output Unit, please refer to the XP95 Output Unit PIN Sheet,
PP2018.
N/C
COM
N/O
3mA
720µA
3.3mA
2
Address Setting
The address of the Output Unit is set using the lower seven segments of the DIL switch. Each segment of
the switch must be set to "0" or "1", using a small screwdriver or similar tool. A complete list of address
settings is shown below.
DIL switch
addr
setting
addr
1234567
1
1000000
11
2
0100000
12
3
1100000
13
4
0010000
14
5
1010000
15
6
0110000
16
7
1110000
17
8
0001000
18
9
1001000
19
10
0101000
20
51
1100110
61
52
0010110
62
53
1010110
63
RELAY
54
0110110
64
OUTPUT
55
1110110
65
1A @ 30V
56
0001110
66
MAX 30V AC
or DC
57
1001110
67
58
0101110
68
59
1101110
69
60
0011110
70
101
1010011
111
102
0110011
112
103
1110011
113
104
0001011
114
105
1001011
115
106
0101011
116
107
1101011
117
108
0011011
118
109
1011011
119
110
0111011
120
Commissioning
It is important that the XP95 Output Unit be fully tested after installation. An XP95 Test Set, part no 55000-
870, may be used to carry out functional testing of individual units. It can also be used to perform data
integrity tests of an entire system.
LED Indicators
!
Relay On
The use of the LEDs can be inhibited by setting the 'LED ENABLE' segment of the DIL switch to '0'.
DIL switch
DIL switch
DIL switch
setting
addr
setting
addr
setting
1234567
1234567
1234567
1101000
21
1010100
31
1111100
0011000
22
0110100
32
0000010
1011000
23
1110100
33
1000010
0111000
24
0001100
34
0100010
1111000
25
1001100
35
1100010
0000100
26
0101100
36
0010010
1000100
27
1101100
37
1010010
0100100
28
0011100
38
0110010
1100100
29
1011100
39
1110010
0010100
30
0111100
40
0001010
1011110
71
1110001
81
1000101
0111110
72
0001001
82
0100101
1111110
73
1001001
83
1100101
0000001
74
0101001
84
0010101
1000001
75
1101001
85
1010101
0100001
76
0011001
86
0110101
1100001
77
1011001
87
1110101
0010001
78
0111001
88
0001101
1010001
79
1111001
89
1001101
0110001
80
0000101
90
0101101
1111011
121
1001111
0000111
122
0101111
1000111
123
1101111
0100111
124
0011111
1100111
125
1011111
0010111
126
0111111
1010111
0110111
1110111
0001111
Illuminated red when relay is energised
3
DIL switch
addr
setting
1234567
41
1001010
42
0101010
43
1101010
44
0011010
45
1011010
46
0111010
47
1111010
48
0000110
49
1000110
50
0100110
91
1101101
92
0011101
93
1011101
94
0111101
95
1111101
96
0000011
97
1000011
98
0100011
99
1100011
100
0010011