Automated Logic G4106 Teknik Talimatlar - Sayfa 2
Kontrol Ünitesi Automated Logic G4106 için çevrimiçi göz atın veya pdf Teknik Talimatlar indirin. Automated Logic G4106 13 sayfaları.
Introduction
The G4106 is a microprocessor-based control module
designed for Direct Digital Control of HVAC equipment.
A single main board provides the power circuitry, the
microprocessor, non-volatile memory, and removable
screw terminals for I/O connections.
Although the G4106 does not provide expansion or
virtual module capability, it can be programmed with up
to 14 Graphic Function Blocks.
Specifications
Power:
24 VAC ±10%, 50-60 Hz, 25VA power
consumption.
Protection:
Built-in surge and transient protection
circuitry. Optically isolated communications.
Memory:
32k byte non-volatile read/write memory, 32k
byte EPROM.
Battery:
Seven year lithium battery provides a
minimum of 10,000 hours of data retention during power
outages.
Rev (29-AUG-97) • Module Driver v4.7
Local Interface:
handheld terminal.
Communication:
Software Requirements:
as FB #15.
Operating Temperature Range:
(-17.8-54.4 °C), non-condensing.
A/D Input Resolution:
Listed By:
Mounting
Mount the G4106 in a panel using the four holes provided
on the cover plate. Be sure to leave about 2 inches on
each side for wiring.
NOTE: The G4106 module must be mounted inside the
building envelope. Mounting outside voids all
warranties.
R
Figure 1: G4106 dimensions
2
Plug-in connector for laptop or
Selectable for 9600 or 38.4k bps.
One G6N module driver
10 bit.
PAZX (UL 916), CSA C22.2.
© 1995-97 Automated Logic Corporation
0-130 °F