Siphon height
Δp - maximum positive / negative working pressure in the compartment of the unit. The height of
condensate drain pipe h = 15 cm is sufficient for vast majority of installations.
Connect one siphon trap (included in delivery) to each condensate outlet. Connect the siphon to the
sewer line.
Make sure that the condensate pipe is passible all the way along including parts inside the unit and
the pipe slope is sufficient.
Fill each siphon trap with water.
4.6.

Installing air filters

The unit is supplied with separately packed filter cassettes. Various filtration classes can be selected
for filters of outdoor, extracted and circulation air: ISO Coarse 60% (G4), ISO ePM10 50% (M5), and
ISO ePM1 55% (F7). Example of filter installation:
o
Filter with class ISO ePM1 55% (F7) as outdoor air filter, location in the compartment e1 (ODA);
o
Filter with class ISO ePM10 50% (M5) as extracted air filter, location in the compartment i1 (ETA).
o
Filter with class ISO ePM10 50% (M5) as circulation air filter, location in the compartment c1 (IDA).
Remove, unpack the cassettes and check their condition. Then install the cassettes in their correct
location based on the unit orientation, see description of the unit in the Chapter 3.1.
Unpack and install air filters last, immediately before putting the unit into service to avoid their
contamination.
Should any damage or contamination be detected, replace the filters with new ones. Spare filter
cassettes are to be ordered from the supplier. The supplier´s address and the spare cassette part
number are shown on the identification plate of the unit.
Insert undamaged clean filters into the guide rails and secure them.
Especially make sure that the arrow showing the direction of air flow through the filter cassette can
be seen from the side of the operator (the arrow is by the unit´s door);
Filter of outdoor air e1(ODA) and extracted air i1(ETA) – the arrow points towards heat
recovery core
Filter of circulation air c1(IDA) – the arrow points towards the supply air fan (see picture)
1
2
ℎ = 1,5
ODA
IDA
ETA
Filter installation
=
+ 50 []
10
=
+ 50 []
2 ∙ 10
+ 100 []
10
10