aqua metro 93533 Montaj Talimatları - Sayfa 9

Ölçüm Cihazları aqua metro 93533 için çevrimiçi göz atın veya pdf Montaj Talimatları indirin. aqua metro 93533 16 sayfaları. M-bus pulse collector / m-bus alarm collector

8.5 Parametrization
Configuration and parameter setting is performed via M-Bus.
The parametrization may be protected from manipulation by setting the so-called
'stop bit' after completion of parametrization and subsequent sealing of the housing
cover. This prevents the stop bit from being reset.
To reparametrize a protected AMBUS
do this, the device must be opened. This involves breaking the safety seal and short-
ing the position designated as 'stop bit' on the PCB.
Following reparametrization or change of date (change of day), AMBUS
enabled.
Parameter settings:
Parameter:
l
Impulse value/unit [
for m
Physical unit *
Medium *
Define initial counter setting *
Text field for description of measuring
point
Primary bus address
Baud rate
Stop bit *
Terminal date
Date/time
Debounce filter *
* protected when stop bit set
bold type designates factory default setting
To parametrize an AMBUS
8.6 Error messages
Error 7:
Other error messages:
8.7 User seal
• Following parametrization, access can be prevented by sealing one of the housing screws with the
safety seal (5) provided.
Montageanleitung/Mounting instructions/Instructions de montage AMBUS
®
IS, the stop bit may be temporarily reset. To
Range
3
0,00001 ... 0.0333. 10,000
] *
3
m
, kWh, MJ or 'no units'
water
hot water
heat / hot side
heat / cold side
steam
electricity
gas
oil
pressurized air
heating cost partition scheme
others
not known
0 ... 1,000,000 **
max. 32 ASCII characters **
0 ... 250
300 / 2400 / 9600
set / not set
DD.MM. 30.06
DD.MM.YY - hh:mm **
activated / deactivated
** data depend on production process.
®
IS you will need our M-Bus programs MBUSTOOL or MBUSTOOL5.
Voltage under or overload
Device defective
®
-IS is automatically dis-
Default value, equivalent to
alarm collector application
1
'no units'
others
(The combinations 'no units' and
'others' defines the alarm collec-
tor)
0
as for AMBUS® IS
as for AMBUS® IS
as for AMBUS® IS
as for AMBUS® IS
as for AMBUS® IS
as for AMBUS® IS
as for AMBUS® IS
®
IS
B-11544
(exclusively)
(exclusively)
(exclusively)
9