Weights and free space requirements
Frame
Weights
size
IP21 (UL
IP55 (UL
Type 1)
Type 12)
kg
lb
kg
R1
4.6
10.1
4.8
R2
6.6
14.6
6.8
R3
11.8
26.0
13.0
R4
19.0
41.9
20.0 44.1
R5
28.3 62.4
29.0 64.0
R6
42.4 93.5 43.0 94.8
R7
54
119.1
56
R8
69
152.2
77
R9
97
213.9 103
1) Without free space on the sides.
2)
Measured from the drive frame, not from the cable box.
Ambient conditions
This table shows the requirements for the ambient conditions when the drive is in operation (installed for stationary use).
Installation altitude
Surrounding air temperature
Relative humidity
Contamination levels
(IEC 60721-3-3: 2002)
Vibration (IEC 60068-2)
Shock/Drop (ISTA)
Safe torque off (STO)
The drive has a Safe torque off function (STO) in accordance with IEC/EN 61800-5-2. It can be used, for example, as the final
actuator device of safety circuits that stop the drive in case of danger (such as an emergency stop circuit).
When activated, the STO function disables the control voltage for the power semiconductors of the drive output stage, thus
preventing the drive from generating the torque required to rotate the motor. The control program generates an indication
31.22
as defined by parameter
activation switch deactivates the STO. Any faults generated must be reset before restarting.
The STO function has a redundant architecture, that is, both channels must be used in the safety function implementation.
The safety data given is calculated for redundant use, and does not apply if both channels are not used.
WARNING! The STO function does not disconnect the voltage from the main and auxiliary circuits of the drive.
Notes:
•
If stopping by coasting is not acceptable, stop the drive and machinery using the appropriate stop mode before
activating the STO.
•
The STO function overrides all other functions of the drive.
Wiring
The safety contacts must open/close within 200 ms of each other.
Double-shielded twisted-pair cable is recommended for the connection. The maximum length of the cabling between the
switch and the drive control unit is 300 m (1000 ft). Ground the shield of the cable at the control unit only.
Validation
To ensure the safe operation of a safety function, a validation test is required. The test must be carried out by a competent
person with adequate expertise and knowledge of the safety function. The test procedures and report must be
documented and signed by this person. Validation instructions of the STO function can be found in the drive hardware
manual.
Free space requirements for vertical installation
IP21 (UL Type 1)
Above
Below
lb
mm
in
mm
in
10.6
150
5.9
86
3.4
15.0
150
5.9
86
3.4
28.7
200
7.9
53
2.1
53
2.1
200
7.9
100
4.0
200
7.9
155
6.1
300
11.8
123.5 155
6.1
300
11.8
169.8 155
6.1
300
11.8
227.1 200
7.9
300
11.8
0 ... 4000 m (0 ... 13123 ft) above sea level. The output current must be derated at
altitudes above 1000 m (3281 ft). The derating is 1% for each added 100 m (328 ft)
above 1000 m (3281 ft).
Above 2000 m (6562 ft), these grounding systems are permitted: TN-S (center-
grounded wye), TT, and IT (ungrounded or high-resistance symmetrically grounded).
For the installation requirements for corner-grounded systems at this altitude,
contact your local ABB representative.
Operation: -15 ... +50 °C (5 ... 122 °F). No frost permitted. At temperatures over 40 °C
(104 °F), the rated output current must be derated by 1% for each added 1 °C (1.8 °F).
Storage (in the package): -40 to +70 °C (-40 to +158 °F).
5 ... 95%. No condensation permitted. Maximum permitted relative humidity is 60%
in the presence of corrosive gases.
Chemical gases: Class 3C2.
Solid particles: Class 3S2. No conductive dust permitted.
Max. 1 mm (5 ... 13.2 Hz), max. 7 m/s
Not permitted
. If the motor is running when Safe torque off is activated, it coasts to a stop. Closing the
Stand alone
IP55 (UL Type 12)
2)
2)
Above
Below
mm
in
mm
in
137
5.4
116
4.6
137
5.4
116
4.6
200
7.9
53
2.1
53
2.0
200
7.9
100
4.0
200
7.9
155
6.1
300
11.8
155
6.1
300
11.8
155
6.1
300
11.8
200
7.9
300
11.8
2
(13.2 ... 100 Hz) sinusoidal
Side by side
All types
All types
Sides
Above
Below
mm
in
mm
in
mm
150
5.9
200
7.9
200
150
5.9
200
7.9
200
150
5.9
200
7.9
200
150
5.9
200
7.9
200
150
5.9
200
7.9
200
150
5.9
200
7.9
300
150
5.9
200
7.9
300
150
5.9
200
7.9
300
150
5.9
200
7.9
300
15
1)
2)
in
7.9
7.9
7.9
7.9
7.9
11.8
11.8
11.8
11.8