Technical data

Minimum voltage at IN1 and IN2 to be interpreted as "1": 13 V DC
STO reaction time (shortest detectable break): 1 ms
STO response time: 2 ms (typical), 5 ms (maximum)
Fault detection time: Channels in different states for longer than 200 ms
Fault reaction time: Fault detection time + 10 ms
STO fault indication (parameter
STO warning indication (parameter
Safety integrity level (EN 62061): SIL 3
Performance level (EN ISO 13849-1): PL e
The drive STO is a type A safety component as defined in IEC 61508-2.
For the full safety data, exact failure rates and failure modes of the STO function, refer to the drive hardware manual.
Markings
The applicable markings are shown on the type designation label of the drive.
CE
UL

Related documents

Document
ACH580-01 (0.75 to 250 kW, 1.0 to 350 hp) hardware manual
ACH580 HVAC control program firmware manual
ACx-AP-x assistant control panels user's manual
Drive composer PC tool user's manual
Converter module capacitor reforming instructions

Declarations of Conformity

EU Declaration of Conformity
Machinery Directive 2006/42/EC
xxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx xxxxxxxxxxxxxxxxxxxxxxxxxxx
We
Manufacturer:
ABB Oy
Address:
Hiomotie 13, 00380 Helsinki, Finland.
Phone:
+358 10 22 11
declare under our sole responsibility that the following product:
Frequency converters
ACH580-01/-31
with regard to the safety function
Safe Torque Off
is in conformity with all the relevant safety component requirements of EU Machinery Directive 2006/42/EC, when the listed safety function
is used for safety component functionality.
The following harmonized standards have been applied:
EN 61800-5-2:2007
Adjustable speed electrical power drive systems – Part 5-2: Safety
requirements - Functional
EN 62061:2005
Safety of machinery – Functional safety of safety-related electrical, electronic
+ AC:2010 + A1:2013 + A2:2015
and programmable electronic control systems
EN ISO 13849-1:2015
Safety of machinery – Safety-related parts of control systems. Part 1: General
requirements
EN ISO 13849-2:2012
Safety of machinery – Safety-related parts of the control systems. Part 2:
Validation
EN 60204-1:2018
Safety of machinery – Electrical equipment of machines – Part 1: General
requirements
The following other standards have been applied:
IEC 61508:2010, parts 1-2
Functional safety of electrical / electronic / programmable electronic safety-
related systems
IEC 61800-5-2:2016
Adjustable speed electrical power drive systems – Part 5-2: Safety
requirements - Functional
The product(s) referred in this Declaration of conformity fulfil(s) the relevant provisions of other European Union Directives which are
notified in Single EU Declaration of conformity 3AXD10000497691.
Person authorized to compile the technical file:
Name and address: Jussi Vesti, Hiomotie 13, 00380 Helsinki, Finland.
Helsinki, March 30, 2021
Signed for and on behalf of:
Tuomo Tarula
Local Division Manager, ABB Oy
Document number 3AXD10000437229
31.22
) delay: < 500 ms
31.22
) delay: < 1000 ms
RCM
EAC
EIP green
Harri Mustonen
Product Unit Manager, ABB Oy
WEEE
TÜV Nord
Declaration of Conformity
Supply of Machinery (Safety) Regulations 2008
xxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx
We
Manufacturer:
ABB Oy
Address:
Hiomotie 13, 00380 Helsinki, Finland.
Phone:
+358 10 22 11
declare under our sole responsibility that the following product:
Frequency converters
ACH580-01/-31
with regard to the safety function
Safe Torque Off
is in conformity with all the relevant safety component requirements of the Supply of Machinery (Safety) Regulations 2008, when the listed safety
function is used for safety component functionality.
The following harmonized standards have been applied:
EN 61800-5-2:2007
Adjustable speed electrical power drive systems – Part 5-2: Safety requirements -
Functional
EN 62061:2005
Safety of machinery – Functional safety of safety-related electrical, electronic and
+ AC:2010 + A1:2013 + A2:2015
programmable electronic control systems
EN ISO 13849-1:2015
Safety of machinery – Safety-related parts of control systems. Part 1: General
requirements
EN ISO 13849-2:2012
Safety of machinery – Safety-related parts of the control systems. Part 2:
Validation
EN 60204-1:2018
Safety of machinery – Electrical equipment of machines – Part 1: General
requirements
The following other standards have been applied:
IEC 61508:2010, parts 1-2
Functional safety of electrical / electronic / programmable electronic safety-
related systems
IEC 61800-5-2:2016
Adjustable speed electrical power drive systems – Part 5-2: Safety requirements -
Functional
The product(s) referred in this declaration of conformity fulfil(s) the relevant provisions of other UK statutory requirements, which are notified in
a single declaration of conformity 3AXD10001325928.
Person authorized to compile the technical file:
Name and address: Jussi Vesti, Hiomotie 13, 00380 Helsinki, Finland.
Helsinki, March 30, 2021
Signed for and on behalf of:
Tuomo Tarula
Local Division Manager, ABB Oy
Document number 3AXD10001329521
16
UKCA
CSA
Code (English)
3AXD50000044839
3AXD50000027537
3AUA0000085685
3AUA0000094606
3BFE64059629
xxxxxxxxxxxxxxxxxxxxxxxxxxx
Harri Mustonen
Product Unit Manager, ABB Oy