21-EN
Ceiling type
8

Applicable Controls

REQUIREMENT
• When this air conditioner is used for the first time, it
takes approx. 5 minutes until the remote control
becomes available after power-on. This is normal.
<When power is turned on for the first time after
installation>
It takes approx. 5 to 10 minutes until the remote
control becomes available.
Approx. 5 to 10 minutes
"SETTING"
"SETTING"
Remote
Power
on
flashes
goes out
control is
available
<When power is turned on for the second (or later)
time>
It takes approx. 3 to 10 minute until the remote
control becomes available.
Approx. 3 to 10 minutes
"SETTING"
"SETTING"
Remote
Power
on
flashes
goes out
control is
available
• Normal settings were made as factory default.
Change the indoor unit settings as required.
• Use the wired remote control to change the
settings.
* The settings cannot be changed using the
wireless remote control, simple wired remote
control, or central control system. Therefore,
install the wired remote control to change the
settings.
Installation Manual
Changing applicable control
setting
Basic procedure for changing settings
Change the settings while the air conditioner is not
working.
(Stop the air conditioner before making settings.)
1
3
4
6
1
5
2
1
Procedure
Push
button and temp. setup
button
simultaneously for 4 seconds or more.
After a while, the display flashes as shown in the figure.
Confirm that the CODE No. is [01].
• If the CODE No. is not [01], push
button to erase
the display content, and repeat the procedure from
the beginning.
(No operation of the remote control is accepted for a
while after
button is pushed.)
(While air conditioners are operated under the group
control, "
" is displayed first.
When
button is pushed, the indoor unit
number displayed following "ALL" is header unit.)
(* Display content varies with the
indoor unit model.)
2
Procedure
Each time
button is pushed, indoor unit
numbers in the control group change cyclically. Select
the indoor unit to change settings for.
The fan of the selected unit runs and the louvers start
swinging. The indoor unit can be confirmed for which to
change settings.
– 11 –
Ceiling type
3
Procedure
Specify CODE No. [
] with temp. setup
buttons.
4
Procedure
Select SET DATA [
] with timer time
buttons.
5
Procedure
Push
button. When the display changes from
flashing to lit, the setup is completed.
• To change settings of another indoor unit, repeat
2
from Procedure
.
• To change other settings of the selected indoor unit,
3
repeat from Procedure
.
Use
button to clear the settings.
To make settings after
button was pushed, repeat
2
from Procedure
.
6
Procedure
When settings have been completed, push
to determine the settings.
When
button is pushed, "SETTING" flashes and
then the display content disappears and the air
conditioner enters the normal stop mode.
(While "SETTING" is flashing, no operation of the
remote control is accepted.)
Installing indoor unit on high
ceiling
When the height of the ceiling to be installed exceeds
3.5 m (11'6"), adjustment of fan speed is necessary.
Set up the high ceiling.
• Set according to the basic operation procedure
1
2
3
4
5
6
(
).
• CODE No. in Procedure specifies [5d].
• Select [SET DATA] in Procedure from "List of
installable ceiling height" in this Manual.
3
• For the CODE No. in Procedure
, specify [5d].
4
• For the SET DATA in Procedure
, select the setup
data of high ceiling to be set up from the table on the
below.
(Exchange by wired remote control)
SET DATA
Standard
0000
11'6" (3.5 m) or less
(Factory default)
more than 11'6" (3.5 m)
0001
High ceiling 1
up to 13'1" (4.0 m)
Installation Manual
Remote control-less setting
/
To set the unit to high ceiling setting, there is a method
that requires the changing of the short plugs on the
indoor P.C. board. The details are shown in the below
table.
/
This method is only to be used where a wired remote
control (Group control) is not used.
* However, once the setting is changed, it is
necessary to reset the setting back to 0000 that
placing the short plugs back to the factory default
position and rewriting the setting data back to 0000
with wired remote control.
• Select by exchange of short plugs on indoor P.C.
board.
Short plug
position
SET DATA
button
Short
Open
Standard (Factory
0000
default)
0001
High ceiling 1
• Short plugs position (CN112, CN111, CN110 from
the left)
22-EN
Note