ARIS LINEARIS Kullanım Talimatları Kılavuzu - Sayfa 10
Kontrolör ARIS LINEARIS için çevrimiçi göz atın veya pdf Kullanım Talimatları Kılavuzu indirin. ARIS LINEARIS 16 sayfaları. Damper actuator
4.5.2
Wiring diagram
S1L
Limit switch, CCW
S2R
Limit switch, CW
S3
Auxiliary switch 1 (Option)
S4
Auxiliary switch 2 (Option)
S5
Auxiliary switch 3 (Option)
S6
Auxiliary switch 4 (Option)
R1
Potentiometer 1
R2
Potentiometer 2 (Option)
HZ
Heating
M
Current output (Option)
K1
Relais for parallel operation
(Option)
!
ADVICE
5.
Operation of the actuators
5.1
Set up rotation direction
Due to the internal wiring, the rotation direction (viewing direction is through the actuator towards the shaft) and the limit switches
assign as follows:
1.
With line voltage on terminal 1 and 2, the actuator shaft rotates counter-clockwise and results in a pushing stroke.
Limitation of this stroke with lower switch S1L. When the switch is activated, line voltage is on terminal 4.
With line voltage on terminal 1 and 3, the actuator shaft rotates clockwise and results in a pulling stroke. Limitation of this
2.
stroke with lower switch S2L. When the switch is activated, line voltage is on terminal 5.
3.
If the actuator runs counterrotating to the commands, change the external connection of terminal 2 and 3 .
!
ADVICE
AGS-Stellantriebe GmbH
Görlitzer Str. 2
D - 33758 Schloß Holte
10
M
C
B
A B
L 0 R
PE
N
Anschlussvariante / Alternative connection
All auxiliary switches must be operated within the same voltage range. Do not mix line
voltage with low voltage.
For options follow the wiring diagrams inside the actuator.
Depending on the model, limit switches may be arranged different than drawn in the wiring
diagram (see wiring diagram inside the actuator).
Datum:
31.03.2007
S1L
S2R
S3
2 3 4 5
6 7 8 9 10 11
1
N
L
SP AC + 2ZW + P + Hz
R1
HZ
S4
18 19 20
27 28
N L
LINEARIS