Whirlpool UXI0600DYS Kurulum Talimatları Kılavuzu - Sayfa 5
Havalandırma Davlumbazı Whirlpool UXI0600DYS için çevrimiçi göz atın veya pdf Kurulum Talimatları Kılavuzu indirin. Whirlpool UXI0600DYS 20 sayfaları. 600 cfm and 1200 cfm in-line blowers for range hoods
Ayrıca Whirlpool UXI0600DYS için: Ürün Boyutları (1 sayfalar)
Calculating
Vent System Length
To calculate the length of the system you need, add the
equivalent length for each vent piece used in the system.
Vent Piece
Equivalent Length
45 ° elbow
2.5 ft
(0.8 m)
90 ° elbow
5.0 ft
(1.5 m)
The maximum equivalent vent lengths are:
10" (25.4 cm) round vents - 60 ft (18.3 m)
Example vent system
90oelbow
_
6 ft (1.8 rn)___l
Wall cap
The following example falls within the maximum recommended
vent length.
1 - 90 ° elbow
= 5.0 ft (1.5 m)
1 - wall cap
= 0.0 ft (0.0 m)
8 ft (2.4 m) straight
= 8.0 ft (2.4 m)
Length of system
= 13.0 ft (3.9 m)
Observe all governing codes and ordinances.
Ensure that the electrica( insta(lation is adequate and in
conformance
with Nationa( Electrical Code, ANSI/NFPA 70 (latest
edition), or CSA Standards C22.1-94, Canadian Electrica( Code,
Part 1 and C22.2 No. 0-M91 (latest edition) and all local codes
and ordinances.
If codes permit and a separate ground wire is used, it is
recommended
that a qualified electrician determine that the
ground path is adequate.
A copy of the above code standards can be obtained from:
National Fire Protection Association
One Batterymarch
Park
Quincy, MA 02269
CSA Internationa(
8501 East Pleasant Valley Road
Cleveland, OH 44131-5575
•
A 120 volt, 60 Hz., AC only, 15-amp, fused electrical circuit is
required.
•
If the house has aluminum wiring, follow the procedure
below:
1. Connect a section of solid copper wire to the pigtail
leads.
2. Connect the aluminum wiring to the added section of
copper wire using special connectors
and/or tools
designed and UL listed for joining copper to aluminum.
Follow the electrical connector manufacturer's
recommended
procedure. Aluminum/copper
connection must conform with
local codes and industry accepted wiring practices.
Wire sizes and connections
must conform with the rating of
the appliance as specified on the model/serial
rating plate.
The model/serial
plate is located behind the filter on the rear
wall of the range hood.
Wire sizes must conform to the requirements of the National
Electrical Code, ANSI/NFPA 70 (latest edition), or CSA
Standards C22.1-94,
Canadian Electrical Code, Part 1 and
C22.2 No. 0-M91 (latest edition) and all local codes and
ordinances.