Before connecting the air dryer, the following items must be checked:
Ø Does the mains voltage coincide with the voltage of the appliance? (Voltage
at AP 50 and AP 70 is 230V / 50 Hz)
Ø Adequate fusing of supply system?
Ø Has the required residual-current-operated circuitbreaker (r.c.c.b) been installed
in case of swimming baths?
Ø For the electrical connection of the dryer is the cover of the connection box to
remove (left above on the back of the dryer, see to figure 4.1 - pos. 3).
Ø Behind it the connecting terminals for 230 V / 50 Hz are placed.
Ø The mains cable is led by the cable entries placed under the connection box into
the connection box. (see figure 4.1, pos. 4)
Ø The connection may take place only via a trained electrician.

6.4 Condensate removal

At the condensate connector (factory-installed left down at the machine) the
enclosed hose (15 x 2 mm) has to be fixed with a clamp.
Lead the hose with downward gradient (at least 5%, i.e. 5 cm/per meter) away from
the dryer into a discharge.
Ø
Ø The condensate connector is factory-installed left down at the machine.
Depending on the situation in the room, the connector can also be changed to
the right side of the dryer:
Remove front cover (without tool, pull off simply)
o
Down at the front you find two screws for the condensate sump.
o
Remove these screws.
Remove the two rubber-plugs at the reverse side of the unit (see
o
figure 5.1, Pos. 8) Remove the screws behind the rubber-plugs.
Now the condensate sump can be removed. Turn it from left to
o
right and insert it back.
Fix the four screws again (front and reverse side). Insert the
o
rubber-plugs again.
Fix the front cover again.
o
Fix the hose now at connector the right side as explained above.
o
ATTENTION:
Ø The end of the hose must be situated lower than the beginning of the hose
(runoff socket)(minimum 5 cm slope on each metre).
Ø The hose end should not be in water, since it can come in such a way to a
water back pressure in the hose.
Ø The hose must never be bent!
Ø No objects must be placed onto the hose!
Ø Check regularly whether the condensate can flow off certainly. Otherwise, a
new hose might be mounted.
page 10 of 17