Overview
This manual explains the installation and operation of the
7551 LDT Interface Module.
Utilizing licensed Allen-Bradley SLC 500™ I/O inter-
face technology, the one slot 7551 LDT Interface Module
accepts one transducer input and plugs directly into the
A-B SLC 500 rack. Communicating through I/O
registers assigned to the slot, the module supplies abso-
lute position and velocity data to A-B SLC™ processors
from AMCI, Balluf or Temposonics™ II magnetostric-
tive linear displacement transducers (LDTs).
Front Panel Description
Two LEDs on the front panel shows the modules'
operating status.
LDT
INTERFACE
7551
The transducer input connector, located behind the
module door, accepts the 8 pin Phoenix connector
(AMCI Part # MS-8) from the transducer cable. The
transducer cable wiring diagram is shown under "Cable
Installation". The 7551 uses the following transducers:
•
AMCI LHT Series LDT
•
MTS Temposonics II LDT with DPM or RPM
Personality Modules
•
Balluff LDT with 'K2' output / power supply
option.
The 7551 module requires an external ±15 Vdc supply
for LDT operation. Power supply current rating is
based on the actual LDT.
ADV ANC ED
MIC RO CON T RO L S INC.
S
7500 I
ERIES
RUN - This green LED is on
when the module is operational.
FAULT - This red LED is
blinking when there is a trans-
ducer fault, or on when there is a
module fault. There are four
major causes of a transducer
fault.
•
Broken transducer cable.
•
Non-compatible transducer.
•
Improperly wired transducer
cable.
•
Faulty transducer.
LDT I
NTELLIGENT
Table of Contents
Overview .................................................... 1
Front Panel Description.............................. 1
Installation .................................................. 2
Software Configuration ................................ 4
7551 Programmable Parameters ................ 4
Data Format ................................................ 5
Programming from the Processor .............. 6
Important User Information ....................... 8
Standard Warranty ...................................... 8
Returns Policy ............................................ 8
24 Hour Technical Support Number .......... 8
Revision History ......................................... 8
Plymouth Industrial Park, Terryville CT 06786
Tel: (203) 585-1254 Fax: (203) 584-1973
M
NTERFACE
ODULE