Akw T301 Інструкції з монтажу, обслуговування та експлуатації - Сторінка 2
Переглянути онлайн або завантажити pdf Інструкції з монтажу, обслуговування та експлуатації для Сантехнічний виріб Akw T301. Akw T301 16 сторінок. Basin mixer valve
Introduction
The THERMOSTATIC MIXING VALVE (T301) is designed to comply with the N.H.S Estate
Model Engineering Specification-D08.
The T301 is approved for use in the following designations.
The following abbreviated designation codes are used throughout this manual.
Approved for the following designations
Code
HP-W
LP-W
Product Description
The T301 is a lever operated sequential mixing valve for basins. It uses proven
thermostatic technology for temperature control. A single lever provides sequential
operation from OFF through COLD and WARM to a maximum blend temperature
preset at 41°C, which can be adjusted if required.
The T301 is designed for single or two hole basins. The supply connections are via
flexible inlet tails which incorporate non return check valves and filters.
The installation must be in accordance with Water Regulations and Bylaws.
The T301 is designed to deliver water consistently at a safe temperature.
In keeping with every other mechanism, the mixer tap cannot be considered as being
functionally infallible therefore the tap cannot totally replace the vigilance of nursing/
supervisory staff where that is necessary. Provided it is installed, commissioned,
operated and maintained within these recommendations, the risk of failure is not
eliminated but can be reduced to a minimum.
SITE REQUIREMENTS
Water pressure requirements - Running water pressure: Mains fed - 0.2 bar min. - 5.0
bar max. Maximum static water pressure: Gravity and mains - 10 bar. The T301 is
designed for higher pressure systems found in the UK up to a maximum of 5 bar running
(dynamic) pressure. For effective operation of the internal seals, the maximum static
pressure must not be exceeded.
Water minimum flow rate. For best performance within the specified running pressure
range a minimum flow of 8 litres per minute should be available to both inlets.
Water temperature requirements. Maximum hot water temperature: = 80°C
Recommended maximum: = 65°C Minimum hot water temperature: = 55°C
Maximum cold water temperature: = 20°C
Operation Pressure
High Pressure
Low Pressure
2
Application
Wash Basin
Wash Basin