GSCM Adjustment Chart
Adjustment Formulas
0 - 60 Second/min/Vbat
0 – 120 (Sec)
15 – 75 Hz
Adjustment
0 - 60 Second Crank Delay
Maximum crank time
Load transfer delay
Load pre-off delay
Battery charge cut-in
Battery charge cut-out
Under speed shutdown
Over speed shutdown
Run/crank disconnect
30 day exercise runtime
* Both battery cut-in and cut-out must be at maximum for switched auto start.
** Both Over Hz and Under Hz must be set at zero to disable the Over or Under Hz Shutdown.
www.atkinsonelectronics.com
800.261.3602
TPV = (Desired Value ÷ 60) x 5
TPV = (Desired Sec ÷ 120) x 5
TPV = {(Desired Hz - 15) ÷ 60} x 5
0 Volts
5 second minimum
Will not energize starter
Ignition and load relays energize together
Ignition and load relays de-energize together
Ignores automatic battery charge function
Ignores automatic battery charge function
Ignores under speed shutdown condition**
Ignores over speed shutdown condition**
Uses 15Hz to disconnect starter
Deactivates 30 day exercise
Example: 11.5V Bat = 0.96V (TPV)
Factory Default Adjustments
Crank Delay
Maximum Crank
Load Transfer Delay
Load Pre-Off Delay
Battery Cut-In Volt
Battery Cut-Out Volt
Under Speed Shutdown
Over Speed Shutdown
Run/Crank Disconnect
30 Day Exercise Runtime @ deactivated - TPV = 0
10
55Hz = 3.33V (TPV)
65Hz = 4.17V (TPV)
@ 5s - TPV = 0.42V
@ 15s - TPV = 1.25V
@ 60s - TPV = 5V
@ 90s - TPV = 3.75V
@ 11.5V - TPV = 0.96V
@ 13.5V - TPV = 1.13V
@ deactivated - TPV = 0
@deactivated - TPV = 0
@ 30Hz - TPV = 1.25V
5 Volts
60 seconds
60 seconds
60 seconds
120 seconds
Switched auto start*
Switched auto start*
75Hz under speed shutdown
75Hz over speed shutdown
Over 60 Hz starter won't disconnect
1 hour 30 day run time