7.3

Semiconductor Fuses

Semiconductor fuses can be used with CSX
transient overload currents and for Type 2 coordination. CSX
Type 2 coordination with semiconductor fuses. Suitable Bussmann and Ferraz semiconductor fuses are
detailed below.
SCR I
Model
CSXi-007
CSXi-015
CSXi-018
CSXi-022
CSXi-030
CSXi-037
CSXi-045
CSXi-055
CSXi-075
168000
CSXi-090
245000
CSXi-110
320000
7.4

General Technical Data

Mains Supply
Mains voltage (L1, L2, L3)
V4
............................................................................................................. 3 x 200 VAC ~ 440 VAC (+ 10% / - 15%)
V6
............................................................................................................. 3 x 200 VAC ~ 575 VAC (+ 10% / - 15%)
Mains frequency (at start)
Rated insulation voltage
Form designation
Control Voltage (A1, A2, A3)
CSXi-xxx-xx-C1
................................................................................................................................................. or 380-440 VAC (+ 10% / - 15%)
CSXi-xxx-xx-C2
Current consumption (during run)
Current consumption (inrush)
CSXi-xxx-xx-C1...................................................................................................................................................................... 10 A
CSXi-xxx-xx-C2......................................................................................................................................................................... 2 A
Inputs
Start (terminal 01)
............................................................................................................... 150 k @ 300 VAC and 5.6 k @ 24 VAC/VDC
Stop (terminal 02) ................................................................................................................................................ Normally closed
............................................................................................................... 150 k @ 300 VAC and 5.6 k @ 24 VAC/VDC
710-02408-00H
Ferraz Fuse
2
T
European/IEC Style
2
(A
S)
(North American Style)
6.6URD30xxxA0063
1150
(A070URD30xxx0063)
6.6URD30xxxA0125
8000
(A070URD30xxx0125)
6.6URD30xxxA0160
10500
(A070URD30xxx0160)
6.6URD30xxxA0160
15000
(A070URD30xxx0160)
6.6URD30xxxA0160
18000
(A070URD30xxx0160)
6.6URD30xxxA0250
51200
(A070URD30xxx0250)
6.6URD30xxxA0315
80000
(A070URD30xxx0315)
6.6URD30xxxA0315
97000
(A070URD30xxx0315)
6.6URD31xxxA0450
(A070URD31xxx0450)
6.6URD31xxxA0450
(A070URD31xxx0450)
6.6URD31xxxA0450
(A070URD31xxx0450)
xxx = Blade Type. Contact Ferraz for options.
.................................................................................................................................
................................................................................................................................................... 600 VAC
.................................................................................
................................................................................................................... 110-240 VAC (+ 10% / - 15%)
....................................................................................................................................
.........................................................................................................................
.................................................................................................................................................
i
soft starters to reduce the potential for damage to SCRs from
i
soft starters have been tested to achieve
Bussmann Fuse
Square Body
Bypassed semiconductor motor starter form 1
CSXi
SPECIFICATIONS
Bussmann Fuse
British Style (BS88)
(170M)
170M-1314
63 FE
170M-1317
160 FEE
170M-1318
160 FEE
170M-1318
180 FM
170M-1319
180 FM
170M-1321
250 FM
170M-1321
250 FM
170M-1321
250 FM
170M-1322
500 FMM
170M-3022
500 FMM
170M-3022
500 FMM
45 Hz to 66 Hz
24 VAC/VDC (± 20%)
Normally open
< 100 mA