Anywire ASLINKAMP LA-A1AW Посібник з експлуатації - Сторінка 7

Переглянути онлайн або завантажити pdf Посібник з експлуатації для Сенсорні термінали Anywire ASLINKAMP LA-A1AW. Anywire ASLINKAMP LA-A1AW 12 сторінок. Anywireaslink system, analog input unit ch insulated type with 7-segment

[Various settings]
■Item

Address setting

Parameter setting

■Common procedure for address writer operation
Be sure to connect to the AnyWireASLINK master unit to use.
The operation requires the address writer ARW-03 (Ver.2.10 or
higher) or ARW-04 (Ver.04-1.00 or higher).
Refer to the address writer's Products Guide for details of the
operation method.
1. Connect the AnyWireASLINK slave to the master unit of the
AnyWireASLINK system.
Transmission signal is required to write and read setting items.
Set with the address writer while supplying the transmission signal to the
transmission lines (DP, DN) of the terminal.
Transmission
signal
Analog input unit
* Make sure to use a 24V DC stabilized power supply for the power supply to be connected.
2. Setting is required for all AnyWireASLINKs devices.
Open the protection cover of the set analog input unit and direct the
address writer to the setting port of the unit as shown in Fig.1 to set.
(Put the light emitting and receiving surface as close to the setting port as
possible.) Close the cover of the other units which are not set.
Setting port
LINK
V
mA
ALM
Fig. 1
Analog port
e-CON (3P)
Address setting
■Address No. setting
An address number is set as a beginning number from which part of the
transmission frame is occupied to the unit.
Set any address number other than "255." The weight is "bit."
The factory address-number setting of the unit is
CAUTION
"255," which means no setting.
In this state, do not perform an address automatic
recognition (refer to the Manual of the master unit).
If the address number setting is "255," the unit
cannot perform an input/output operation.
Make sure to use the terminal after setting the
address number within the range of "0 to 254."
Ex.) Address correspondence of a quadruple analog input unit
AnyWire address
0
16
32
48
Input
"0" "16" "32" "48"
Setting address
Red: DP
AnyWireASLINK
Master
Black: DN
24V DC*
Setting port
When setting,
open the protection
cover.
63
Parameter setting
■Input specifications setting
Set the input speci cations of the analog.
- Address writer (ARW-04, ARW-03): Parameter 01
Variable
speci cations
0
0
0-10V
0-10V
1
1
0-5V
0-5V
2
2
1-5V
1-5V
3
3
0-20mA
0-20mA
4
4-20mA
4-20mA
When receiving the transmission signal and starting, the unit displays set
input speci cations for about 3 seconds and then switches them to actual
input value display.
■Setting of average number of moving times
This is the setting of the average number of moving times of analog input.
The average value of the number of setting times +1 is adopted.
- Address writer (ARW-04, ARW-03): Parameter 03
Variable
0
Average number of moving times once
0~31
Setting range 0 to 31 (Average of MAX 32 times)
■Address/parameter automatic setting (base unit only)
This is a function to automatically re ect an address and parameter setting
set to the base unit to the extension unit.
- Address writer (ARW-04, ARW-03): Parameter 17
Variable
Automatic setting unavailable
0
Address/Parameter setting to the base unit and extension unit
respectively.
Address automatic setting
Only the address is automatically assigned to extension units
1
extended from the base unit in series.
Parameter automatic setting
2
Only the parameter is automatically re ected to extension units
extended from the base unit.
Address/parameter automatic setting
The address is automatically assigned to extension units extended
3
from the base unit in series.
The parameter is automatically re ected to extension units extended
from the base unit.
When this automatic setting mode becomes available (value 1, 2, 3), the
255
address or parameter set to the base unit is automatically assigned to
extension units.
They are assigned even when LB-A12W is mixed.
In the "reference shift mode," however, only ON or OFF is re ected.
Set renewal of the reference value individually.
Ex.) Parameter 17
In the case of value 1
Setting address
-L*A1AW 7/12-
Input
7-segment display
Before shipment: 0
Average number of moving times
Address/parameter automatic setting (base unit only)
Before shipment: 0
Assignment
"16"
"0"
LED
indication
V ON
LINK
LINK
V
V
mA
mA
ALM
ALM
V ON
LINK
LINK
V
V
mA
mA
ALM
ALM
V ON
LINK
LINK
V
V
mA
mA
ALM
ALM
mA ON
LINK
LINK
V
V
mA
mA
ALM
ALM
mA ON
LINK
LINK
V
V
mA
mA
ALM
ALM
Before shipment: 0
Supply
Extension
Supply
Base