Automationdirect.com Productivity 1000 P1-04THM Посібник - Сторінка 3
Переглянути онлайн або завантажити pdf Посібник для Системи вводу/виводу Automationdirect.com Productivity 1000 P1-04THM. Automationdirect.com Productivity 1000 P1-04THM 8 сторінок. Analog input
P1-04THM Schematic
MODULE CIRCUITRY
TC1+
TC1-
TC2+
TC2-
TC3+
TC3-
TC4+
TC4-
Sales 800-633-0405
INTERNAL
CH1 T/C
INPUT
CH2 T/C
INPUT
CH3 T/C
INPUT
CH4 T/C
INPUT
P1-04THM Wiring Diagram
Thermocouple Input Circuits
Ungrounded/Shielded
Thermocouple
TC+
TC-
Grounded/Shielded
Thermocouple
TC+
TC-
Infrared
Thermocouple
TC+
TC-
NOTES:
1. Connect shield to thermocouple signal/ground only. Do not connect to
both ends.
2. Install jumper wire on each unused input,
TC+ to TC-.
3. With grounded thermocouples, take precautions to prevent having a
voltage potential between thermocouple tips. A voltage of 1.25V or
greater between tips will skew measurements.
4. Use shielded, twisted thermocouple extension wire that matches the
thermocouple type. Use thermocouple-compatible junction blocks.
www.productivity1000.com
Voltage Input Circuits
TC+
4-wire
Voltage
TC-
Transmitter
Transmitter
AC or DC
Power Supply
TC+
Load Cell
or
TC-
Strain Gauge
Excitation
AC or DC
Power Supply
Voltage Divider
TC+
TC-
TC+
TC-
3