ADEMCO 5806 Інструкція з монтажу - Сторінка 2
Переглянути онлайн або завантажити pdf Інструкція з монтажу для Димова сигналізація ADEMCO 5806. ADEMCO 5806 4 сторінки. Smoke detector with built-in wireless transmitter
Також для ADEMCO 5806: Інструкція з монтажу (5 сторінок)
1. Remove the smoke detector from its
mounting plate by twisting the detector
counterclockwise. If batteries are being
replaced, remove the existing batteries
from their compartments and discon nect
the battery clips.
2. Install the new 9-volt alkaline batteries in
their respective compartments as follows:
Snap the battery contacts onto the
terminals of the first battery (be sure to
observe correct polarity and do not force
battery clips). Holding the contacts on the
battery, install the battery into its
compartment. Make sure the battery is
fully seated (see Figure 1).
Note: If the detector's ID has not been programmed into the system (i.e., this is
an initial detector installation), refer to the
perform the ID "enrolling" procedure before mounting or testing the detector.
Programming
The QED control system must "enroll" the smoke detector's ID during installation of the
system. The QED control should be programmed to "enroll" the 5806 as an "RF" type unit
(i.e., supervised RF), with a loop number of "1." With the QED control in the programming
mode, you can either manually enter the serial number or transmit from the device (push
the "Enroll" button [see Figure 1], install the battery, etc...). See the QED control unit's
installation instructions for further details.
Be sure to verify that the detector has been enrolled into the system by using the procedure
provided in the section on page 6 titled Testing the Smoke Detector .
If a "low battery" message is displayed and you suspect that the batteries are not actually
low, remove both batteries, wait 20 seconds, re-insert them, and re-test the detector.
Repeat this procedure if necessary.
Tamper Protection
For tamper protection, cut the wire jumper indicated in Figure 1. After the detector has been
mounted, a magnet must then be installed on the wall or ceiling next to the detector.
To ensure proper positioning of the magnet after the detector has been mounted, place a
light pencil mark on the side of the detector near the center of the reed switch (see Fig. 1).
9 VOLT
INDEXING
BATTERY
MARK
COMPARTMENTS
INDEXING
MARK
HOLDING TABS.
LOCKING TABS ON MOUNTING PLATE SLIDE BENEATH
THESE TABS (DETECTOR IS LATCHED ONTO MOUNT-
ING PLATE BY TURNING CLOCKWISE)
Figure 1. Bottom View of Smoke Detector (without mounting plate)
– 2 –
Connect the second 9-volt alkaline
battery in a similar manner and install it
in the second compartment.
3. Re-install the smoke detector onto the
mounting plate by turning it clockwise,
and test its operation as described in
the TEST section.
4. The LED indicator should flash about
once every 40 seconds, indicating
normal operation. If the batteries are
not installed correctly, the smoke
detector will not function. If the unit
appears not to be sending a signal
during any of the tests, check for
correct battery installation.
section below and
PROGRAMMING
LOCATION OF "ENROLL" BUTTON
AND "TAMPER" JUMPER
"ENROLL" BUTTON
"ENROLL"
(INSIDE OPENING).
BUTTON
PUSH (WITH SMALL
SCREWDRIVER) TO
SEND "FAULT".
PLACE LIGHT
PENCIL MARK
CUT JUMPER
FOR TAMPER
HERE*
*
ONLY IF TAMPER
MAGNET WILL BE
REED SWITCH
USED
MAGNETIC REED
SWITCH
Mounting The Smoke Detector
First, determine the best location for the
smoke detector (one that provides strong
wireless transmission paths AND proper
smoke
detector
protection).
See
RECOMMENDED LOCATIONS FOR
SMOKE DETECTORS (on next page).
A good RF transmission path must be
established from the proposed mounting
location before permanently installing the
detector. To check, perform the test in
TESTING THE SMOKE DETECTOR.
Mounting Locations
Detectors should be located as close to
the center of the ceiling as possible. If
this is not practical, detectors may be
located on the ceiling up to 4 inches
(10cm) from the ceiling-wall junction. Do
not install near forced air heating or air
conditioning ducts (outlets or returns). For
sloped, gabled or high-peaked ceilings,
detectors must be mounted between 4
and 6 inches (10 and 15cm) from the
highest point in the ceiling.
Detectors may also be wall-mounted.
Check with your local Fire Department
about code requirements. Wall-mounted
detectors should be located 4–6 inches
(10–15 cm) from the ceiling.
In mobile homes, battery-operated
detectors are not generally installed by
the manufacturer. Mount detectors ONLY
on an interior wall.
1. Once a suitable location has been
determined, install the mounting plate
on the ceiling or on the wall. Use the
two screws and anchors provided.
LOCKING TABS
INDEXING MARK
(USED FOR SECURING
SMOKE DETECTOR
TO MOUNTING PLATE)
INDEXING MARK
SLOTTED HOLES
FOR MOUNTING
SCREWS
NOTE:
OTHER SIDE FACES CEILING OR WALL
(THE WORDS "SINGLE GANG" MUST FACE
AWAY FROM MOUNTING SURFACE).
Figure 2. Mounting Details
2. Latch the detector onto the mounting
plate as follows: Position the detector
onto the plate, mating the small center
post on the detector with the "dimple"
at the center of the mounting plate, and
aligning the index marks on the sides
of the plate and the detector. Then turn
the detector in a clockwise direction so
that the holding tabs on the detector
engage the locking tabs on the
mounting plate.
3. If the tamper has been enabled (as
indicated previously), a magnet (No.
39WH-M) should be mounted on the
wall or ceiling surface next to the
detector (1/4" max) in the specified
location (see Fig. 2).
4. Test the detector immediately after
completing the installation and refer to
the QED control system's instructions
for additional information concerning
the use of wireless smoke detectors.
(10 cm)
4 IN.
CEILING
DEAD AIR
BEST IN
ACCEPTABLE
SPACE
CORNER
HERE
NEVER
HERE
ACCEPTABLE
HERE
NOTE:
MEASUREMENTS
SHOWN ARE TO THE
CLOSEST EDGE OF
THE DETECTOR.
1/4" MAX
No.39WH-M MAGNET
NOTE: MAGNET IS
MOUNTED NEXT TO
DETECTOR ON SIDE
OPPOSITE TEST
BUTTON.
TEST BUTTON
INDEXING MARK
INSTALLATION OF MAGNET (FOR TAMPER PROTECTION)
4 IN.
(10 cm)
6 IN.
(15 cm)
SIDE WALL
– 3 –