Automationdirect.com IRONHORSE GSD1-48-10C Посібник користувача - Сторінка 11
Переглянути онлайн або завантажити pdf Посібник користувача для Приводи постійного струму Automationdirect.com IRONHORSE GSD1-48-10C. Automationdirect.com IRONHORSE GSD1-48-10C 12 сторінок.
T
p
a
riM
oT
DjUSTMenTS
Before the power is applied, set the voltage selection jumper to the correct voltage. An incorrect
jumper setting will not damage the drive, but will affect the trim pot adjustments. The speed
potentiometer and trim pots should be preset as follows:
t
P
P
riM
Ot
reset
1) Preset Speed pot fully CCW�
2) Preset MAX trim pot CW 1/2 way�
3) Preset CURRENT LIMIT trim pot fully CW�
4) Preset MIN trim pot fully CCW�
5) Preset ACCEL trim pot CW 1/2 way�
6) Preset IR trim pot fully CCW�
DC power can now be applied to the system and the DC Drive adjusted as follows:
t
P
a
riM
Ot
DjUstMent
7) Increase the MIN trim pot CW until just before reaching an output voltage (deadband), or until the
desired minimum speed is reached�
8) Turn the Speed pot fully CW and adjust the MAX trim pot until the desired maximum speed is
reached�
9) Adjust the ACCEL trim pot to achieve the desired soft start time�
(CW rotation will increase accel time�)
10) Rotate the CURRENT LIMIT trim pot fully CCW� Apply a full load to the motor� While motor is
stalled, adjust the CURRENT LIMIT trim pot CW until a desired current setting is obtained�
(Approximately 125% of rated motor current is recommended�)
11) For 10A models GSD1-48-10C:
Set the Speed pot to approximately 50%, and note the motor RPM� Load the motor to normal load
condition and adjust the IR trim pot CW until motor RPM is equal to the unloaded speed�
For 20A models GSD1-48-20C:
Adjust the IR trim pot CW 1/2 way� If the motor speed is inconsistent ( jumpy), rotate the IR trim pot
CCW until the motor rotation becomes stable�
12) If the voltage selection jumper setting is changed, repeat Trim Pot Preset and Trim Pot Adjustment�
T
roUbleSHooTinG
If a newly installed DC Drive will not operate, it is likely that a terminal connection is loose. Check the
terminal connections and ensure that they are secure and correct. If the drive is still inoperative, refer
to the Troubleshooting Table.
Problem
Motor doesn't run
Motor "hunts"
Motor runs uncontrollably at
"full speed"
Motor rotates in wrong
direction
Motor stalls under a light load
IronHorse GSD1 DC Drives User Manual – 2nd Edition, Revision B – 10/12/2018
Troubleshooting
Possible Cause(s)
1) Incorrect or no power
2) Speed pot set at zero
3) Worn motor brushes
4) Current Limit set too low
1) Max trim pot set too high
2) IR Comp trim pot set too high
1) Loose Speed pot connections
2) Min or Max trim pots improperly
adjusted
3) Possible drive failure
Motor armature hooked up backwards
Current Limit trim pot improperly adjusted
Corrective Action
1) Install proper power service
2) Rotate Speed pot fully CW
3) Replace motor brushes
4) Adjust Current Limit trim pot CW
1) Refer to "Trim Pot Adjustment"
2) Refer to "Trim Pot Adjustment"
1) Secure all connections
2) Refer to "Trim Pot Adjustment
3) Contact ADC Returns for
replacement (800) 633-0405
Reverse armature + and - leads
Refer to "Trim Pot Adjustment"
Page 11