■ Parameter 2 group
Parameter
Display Default Setting range
Input
2-1
KCaH Refer to 'Input Type and Using Range'.
specification
01)
IN-T
Temperature
2-2
?C ℃, ℉
unit
01)
UNIT
Input
2-3
0000 -999 to 999 (-199.9 to 999.9) ℃/℉
correction
IN-B
Input digital
2-4
00)1 0.1 to 120.0 sec
filter
MAvF
2-5
SV low limit
-50 Within 2-1 Input specification Input
02)
L-SV
2-6
SV high limit
02)
H-SV
1200
Control output
2-7
HEAT HEAT: Heating, COOL: Cooling
mode
03)
O-FT
2-8
Control type
PID PID, ONOF: ON/OFF
04)
C-MD
2-9
Control output
RLY RLY: relay, SSR
OUT
SSR drive
2-10
output type
SSrM
STND
2)0
2-11 Control cycle
T
@0
AL1 alarm
2-12
operation
AM!A
□□□.■
AL-1
AL1 alarm
2-13
option
AL2 alarm
2-14
operation
AL2 alarm
AL-2
AM!A
2-15
option
Alarm output
2-16
001 1 to 100 (0.1 to 50.0) ℃/℉
hysteresis
AHYS
2-17 LBA time
LBaT
0000
2-18 LBA band
LBaB
0002
Digital input
2-19
key
DI-K
STOP
Sensor error
2-20
MV
ErMV
00)0
2-21 Lock
LOC
OFF
01) Below parameters are initialized when the setting value is changed.
- Parameter 1 group: AL1/2 alarm temperature
- Parameter 2 group: Input correction, SV high/low limit, Alarm output hysteresis, LBA time, LBA band
- SV setting mode: SV
02) If SV is lower than low limit or higher than high limit when the value is changed, SV is changed to the low/high
limit value.
If 2-1 Input specification is changed, the value is changed to Min./Max. value of Input specification.
03) When the setting value is changed, setting value of 2-20 Sensor error MV is initialized to 0.0 (OFF).
04) When changing the value from PID to ONOF, each value of following parameter is changed.
2-19 Digital input key: OFF, 2-20 Sensor error MV: 0.0 (when setting value is lower than 100.0)
range,
L-SV ≤ H-SV - 1-digit ℃/℉
H-SV ≥ L-SV + 1-digit ℃/℉
[AC model]
STND: standard, CYCL: cycle, PHAS:
phase
0.5 to 120.0 sec
□□□
AM0: Off
AM1: Deviation high limit alarm
AM2: Deviation low limit alarm
AM3: Deviation high, low limit alarm
AM4: Deviation high, low reverse alarm
AM5: Absolute value high limit alarm
AM6: Absolute value low limit alarm
SBA: Sensor break alarm
LBA: Loop break alarm (LBA)
■
A: Standard
B: Alarm latch
alarm
D: Alarm latch and
C: Standby
standby sequence 1
sequence 1
F: Alarm latch and
E: Standby
standby sequence 2
sequence 2
• Enter to option setting: Press [◀] key
in 2-12 AL-1 alarm operation.
Same as 2-12/13 AL1 alarm operation/
option
0 (OFF) to 9999 sec or auto (auto
tunning)
0 (OFF) to 999 (0.0 to 999.9) ℃/℉ or
auto (auto tunning)
STOP: Stop control output, AL.RE:
Alarm reset, AT*: Auto tuning execution,
OFF
0.0: OFF, 100.0: ON
0.0 to 100.0%
OFF
LOC1: Parameter 2 group lock
LOC2: Parameter 1/2 group lock
LOC3: Parameter 1/2 group, SV setting
lock
Function: Alarm
Condition
88* 8
-
Alarm
Alarm
operation
option
-
■ Operation
-
Name
Alarm operation
-
-
-
Deviation
-
high limit
High deviation: Set as 10℃ High deviation: Set as -10℃
-
Deviation
-
low limit
Low deviation: Set as 10℃
-
-
Deviation
high, low
2-9 Control
limit
output: SSR
2-9 Control
Deviation
output: RLY
high, low
2-10 SSR drive
limit reverse
output type:
STND
OFF
2-9 Control
Absolute
output: SSR
value high
2-10 SSR drive
limit
Absolute value: Set as 90℃ Absolute value: Set as 110℃
output type:
STND
Absolute
value low
limit
Absolute value: Set as 90℃ Absolute value: Set as 110℃
Sensor break -
-
Loop break
-
■ Option
Name
Description
Standard
If it is an alarm condition, alarm output is ON. If it is a clear alarm
alarm
condition, alarm output is OFF.
If it is an alarm condition, alarm output is ON and maintains ON
-
Alarm latch
status.
First alarm condition is ignored and from second alarm
Standby
condition, standard alarm operates. When power is supplied
sequence 1
and it is an alarm condition, this first alarm condition is ignored
and from the second alarm condition, standard alarm operates.
Alarm
If it is an alarm condition, it operates both alarm latch and
latch and
standby sequence. When power is supplied and it is an alarm
-
standby
condition, this first alarm condition is ignored and from the
sequence 1
second 1alarm condition, alarm latch operates.
First alarm condition is ignored and from second alarm
2-12/14
condition, standard alarm operates. When re-applied standby
Standby
AL1/2 alarm
sequence and if it is alarm condition, alarm output does
sequence 2
operation:
not turn ON. After clearing alarm condition, standard alarm
AM1 to 6
operates.
Basic operation is same as alarm latch and standby sequence1.
2-12/14
Alarm
It operates not only by power ON/OFF, but also alarm set value,
AL1/2 alarm
latch and
or alarm option changing. When re-applied standby sequence
operation:
standby
and if it is alarm condition, alarm output does not turn ON.
LBA
sequence 2
After clearing alarm condition, alarm latch operates.
2-12/14
AL1/2 alarm
operation:
LBA & 2-18
LBA time: > 0
* 2-8 Control
type: PID
2-8 Control
type: ONOF
2-8 Control
type: PID
-
Set both alarm operation and alarm option by combining.
Each alarm operates individually in two alarm output models.
When the current temperature is out of alarm range, alarm clears
automatically.
OFF
H
ON
OFF
H
ON
SV
PV
PV
SV
100℃
110℃
90℃
100℃
ON
H
OFF
ON
H
PV
SV
SV
PV
90℃
100℃
100℃
110℃
Low deviation: Set as -10℃
ON
H
OFF
H
ON
PV
SV
PV
90℃
100℃
110℃
High, Low deviation: Set as 10℃
OFF
H
ON
H
OFF
PV
SV
PV
90℃
100℃
110℃
High, Low deviation: Set as 10℃
H
ON
OFF
H
ON
PV
SV
SV
PV
90℃
100℃
100℃
110℃
ON
H
OFF
ON
H
PV
SV
SV
PV
100℃
110℃
90℃
100℃
• H: Alarm output hysteresis
Description
No alarm output
If deviation between PV and
SV as high-limit is higher
than set value of deviation
temperature, the alarm
output will be ON.
If deviation between PV
OFF
and SV as low limit is higher
than set value of deviation
temperature, the alarm
output will be ON.
If deviation between PV
and SV as high/low-limit
is higher than set value of
deviation temperature, the
alarm output will be ON.
If deviation between PV and
SV as high/low-limit is lower
than set value of deviation
temperature, the alarm
output will be OFF.
If PV is higher than the
absolute value, the output
will be ON.
OFF
If PV is lower than the
absolute value, the output
will be ON.
It will be ON when it detects
sensor disconnection.
It will be ON when it detects
loop disconnection.
Condition
of re-apply
-
-
Power ON
Power ON,
change SV,
change
alarm
temperature
/ operation
or change
STOP to RUN
mode