SYSTEM SPECIFICATIONS
Maximum Water Pressure: 85psi (8.6 bar)
Maximum Water Temperature: 100°F (38°C)
Inlet/Outlet Connections:
160197: 3/4" (19.05mm) NPT
160198: 1" (25.4mm) NPT
Maximum Flow Rate: up to 8 gpm
Filter Cartridge Life Span
Cartridges should be changed at least every 6 months or sooner
depending on incoming water quality.
Replacement Filters
ITEM #
FREQUENCY
36287
6 Months
36091
6 Months
Notice to Installer
 Do not discard this manual after installation. This manual contains
important operation, maintenance and precautionary information.
Please present this manual to the user/owner/operator after
installation.
 It is strongly suggested that you read this manual before installing
the system to ensure the best possible installation.
 Installation must comply with all local and state plumbing codes
and regulations.
 Connect the system to cold water supply only. Water temperature
cannot exceed 100°F (38°C).
 System must be installed in a vertical, upright, and level position.
 Do not use with water that is microbiologically unsafe or of
unknown water quality.
 Notice to user/owner/operator: please retain this manual for a
future reference for parts, maintenance, or troubleshooting.
 It is recommended that all personnel responsible for operation
and maintenance of this product read the precautions,
maintenance, and operations section of this manual.
2
FILTER
DESCRIPTION
P-PMB-5-20BV,
Sediment
4.5" X 20", 5 Micron
Carbon
P-RF-20BV, 4.5" X 20
Installation Precautions
 Do not install system on line pressure above 85psi. If water pressure
is over 85psi (8.6 bar), Canature WaterGroup recommends the
installation of a pressure regulator.
 Do not install the system on a hot water line. Failure to limit the
water temperature to 100°F (38°C) can result in housing failure and
property damage.
 Do not connect the system backwards with the feed water line
connected to the outlet.
 Do not use liquid pipe thread compounds for threaded connections.
Use Teflon® tape only.
 Do not allow the system to freeze. Turn off water supply and drain
the system if temperature falls below 32°F (0°C).
 Do not install system in direct sunlight or where the system will be
exposed to harsh chemicals or may be subjected to being hit by
moving equipment, carts, mops, or any other item that may cause
damage.
 Allow 3" (76mm) minimum clearance under the housings for filter
replacement.
 If water hammer is evident, install water hammer arrestors before
the system.
 Do not overtighten fitting connections.
 Always back off fittings with a wrench when installing fittings to
avoid overtightening or loosening existing fittings.
 Do not install the unit behind equipment where it may be difficult to
access the system for future filter replacements.
Position the system in a suitable location. The direction of flow
through the system is left to right. Keep this in mind when determining
installation locations. Do not mount the system near any source
of heat. Also, do not mount this system over anything that may be
adversely affected by water.
DIMENSIONS