1.10.1 Fan Speed
1.10.1 Fan Speed
If one or more fans fail on the fan-tray assembly, replace the entire assembly. You cannot replace
individual fans. The red Fan Fail LED on the front of the fan tray illuminates when one or more fans fail.
For fan tray replacement instructions, refer to the Cisco ONS 15454 SDH Troubleshooting Guide. The
red Fan Fail LED clears after you install a working fan-tray assembly.
Fan speed is controlled by TCC2 card temperature sensors. The sensors measure the input air
temperature at the fan-tray assembly. Fan speed options are low, medium, and high. If the TCC2 card
fails, the fans automatically shift to high speed. The temperature measured by the TCC2 sensors is
displayed on the LCD screen.
1.10.2 Air Filter
The ONS 15454 SDH contains a reusable air filter that is installed beneath the fan-tray assembly.
Do not reach into a vacant slot or chassis while you install or remove a module or a fan. Exposed
Warning
circuitry could constitute an energy hazard.
The reusable filter is made of a gray, open-cell, polyurethane foam that is specially coated to provide fire
and fungi resistance. Spare filters should be kept in stock.

1.11 Power and Ground Description

Ground the equipment according to standards or local practices.
The ONS 15454 SDH has redundant –48 VDC power connectors on the MIC-A/P and MIC-C/T/P
faceplates.
To install redundant power feeds, use the two power cables shipped with the ONS 15454 SDH and one
ground cable.
For details, see the
on page
Caution
Only use the power cables shipped with the ONS 15454 SDH.

1.12 Alarm, Timing, LAN, and Craft Pin Connections

Always use the supplied ESD wristband when working with a powered ONS 15454 SDH. Plug the
Caution
wristband cable into the ESD jack located on the lower-right outside edge of the shelf assembly.
The MIC-A/P and the MIC-C/T/P cards in the EFCA area at the top of the ONS 15454 SDH shelf are
used to connect alarm, timing, LAN, and craft connections to the ONS 15454 SDH.
For details, see the
on page
Cisco ONS 15454 SDH Reference Manual, R4.6
1-16
"3.19 MIC-A/P Card" section on page 3-54
3-57.
"3.19 MIC-A/P Card" section on page 3-54
3-57.