Akron 1494 Інструкції з монтажу, експлуатації та обслуговування - Сторінка 2
Переглянути онлайн або завантажити pdf Інструкції з монтажу, експлуатації та обслуговування для Сантехнічний виріб Akron 1494. Akron 1494 12 сторінок. Electric ladder pipe, nozzle
PRODUCT RATINGS FOR SABERMASTER NOZZLE
Standard Flow: Fog 1250 gpm at 80 psi
2" Smooth Bore - 840 gpm at 50 psi, 1188 gpm at 80 psi
Optional Flow: Fog 1000 gpm at 80 psi
1 15/16" Smooth Bore - 789 gpm at 50 psi, 998 gpm at 80 psi
Maximum Pressure: 200 psi/14 bar
Minimum Voltage at motor: 12 Volt Motor: 10 Volts at 15 amps
Maximum Motor Current Draw: 10 amps
Normal Operating Current Draw: 5 amps
PRODUCT WARNINGS FOR ELECTRIC LADDER PIPE
L
!
WARNING:
Aim the Electric Ladder Pipe in a safe direction before pumping water through it.
L
!
WARNING:
Ensure the ladder being used has adequate structural strength to support the reaction force
generated during operation.
L
WARNING:
Although the logic box includes a water resistant coating it is important to keep water out of
!
the controllers and logic box. Prolonged exposure to water will cause damage. When the
cover of the controllers or logic box is removed, check that the O-Ring under the cover is
intact and free of dirt and debris.
L
!
WARNING:
The Electric Ladder Pipe uses current limiting for both the monitor and nozzle stops. Use
only appropriate Akron Brass
L
!
WARNING:
Do not use the electric controls when the override crank is being used or is in position for
use.
L
!
WARNING:
Make the connection of the vehicle and auxiliary battery the final step.
L
!
WARNING:
If any tags or bands are worn or damaged and cannot be easily read, they should be
replaced.
L
!
WARNING:
Disconnect power and disable flow before maintenance.
L
!
WARNING:
Keep all personnel out of the Danger Zone (in front of the outlet of the monitor - See
Dimensional Specifications Figure 1) when the water source is attached. Dangerous flow
velocities can cause serious injury.
L
!
WARNING:
The Electric Ladder Pipe monitor contains moving parts. Keep hands, fingers and
objects away from pinch points (Figure 1).
L
!
WARNING:
Not designed for explosive environments.
PRODUCT WARNINGS FOR SABERMASTER NOZZLE
L
WARNING:
Akron Brass Monitors and Nozzles are matched to a custom engineered electrical control pack-
!
age. Caution must be observed if the SaberMaster is used on a non-Akron Brass style monitor.
In order to prevent mechanical and electrical damage to the SaberMaster nozzle, the control
package being used must have current sense protection that matches the load requirements for
the SaberMaster. The monitor's electrical control package must set the current limit trip point for
the nozzle to 10 amps.
L
WARNING:
The SaberMaster Style 1577 nozzle can produce large reaction forces. The supporting struc-
!
ture must be strong enough to safely withstand a reaction force of up to 600 lbs.
L
WARNING:
Charge slowly to facilitate a controlled water pressure build-up during start up. Rapid charging
!
can cause water hammer.
L
WARNING:
At pressures below that indicated, the nozzle will have reduced flow and reach. Be sure you
!
have enough flow and pressure for the situation (see IFSTA and NFPA manuals for guidelines).
L
WARNING:
Do not use on electrical fires. May result in electrocution.
!
L
WARNING:
Ensure the nozzle is aimed in a direction that is safe, prior to charging.
!
L
WARNING:
Do not use the nozzle as a forcible entry tool. Doing so may damage it or make it inoperable.
!
L
WARNING:
Ensure the thread on the nozzle swivel is matched to the thread on the monitor connection.
!
24 Volt Motor: 20 Volts at 7.5 amps
®
nozzles.
Page 2
L
WARNING
!