bracket on the fan side radiant tube. Position U
bolt tube alignment sections over the tube and
through bracket prior to clamping.
2.2.4 U Bend.
For VS(A) 'U' tube heaters only. Slide the 'U'
bend onto the tube ends with the clamping
bolts facing upwards until the predefined stop
position. Tighten clamping bolt arrangement
using 13mm socket and wrench.
2.2.5 Couplers.
For VS(A)LF, VS(A)LH, VS(A)LI and VS(A)
45/50UT tube heaters only
tubes, locate and position tube couplers at the
end of the tubes so that the socket heads are
facing
outwards.
arrangement to secure ensuring the bolts are
not over tightened.
To avoid damaging the heater whilst
installing
we
chassis be suspended prior to fitting reflectors.
2.2.6 Reflectors
After removing the protective plastic coating,
slip the reflector through the brackets until the
locating slots are aligned with the type A
bracket fixing points.
Slide the next reflector through the brackets
and overlap the existing reflector until the
locating slots line up with the same bracket
fixing points Secure overlapped reflectors to
bracket using M6 nuts, bolts and flat mud
washers.
.
For joining radiant
Tighten
clamping
recommend
the
heater
All reflectors must be positioned/
attached to the brackets exactly as
detailed in the assembly drawings.
2.2.7 End Caps
Position the end cap with no tube holes beneath
the reflector profile at the U bend end with the
end cap flanges facing inwards. Fasten to
reflector using M5 pozi set pin and 'Z' clip.
Position the end cap with tube holes
the reflector profile at the burner end with the
end cap flanges facing inwards. Fasten to
reflector using M5 pozi set pin and 'Z' clip.
bolt
2 x 'Z' clips
2.2.8 Burner Assembly
Slide the burner assembly onto the RIGHT
HAND
TUBE
ensuring it is fully engaged. Secure with grub
screws.
2.2.9 Heat Exchanger Assembly
S
lide the heat exchanger assembly onto the
LEFT HAND TUBE when viewed from above
ensuring it is fully engaged. Secure with pinch
screws.
2.2.10 Detailed Assembly Drawings
The
following
dimensional details of the VSXE heaters.
Please note the heater type, length and
reference number from the delivery/advice note
before identifying the correct model drawing.
4
M5 set pin
These holes -
Burner end only
when viewed from above,
pages
show
the
beneath
End Cap
technical