[Included in the Package]
L□-D□1AW
This product ... 1
*
A connector for an analog device shall be separately purchased.
[Name of Each Part]
Protective cover
LED indicators
7-segment display
Model identi cation label
Analog port,
e-CON (3P)
7-segment display
Model identi cation label
Analog port,
e-CON (3P)
Model
Ch-to-Ch isolated
Current
Voltage
Master
Transmission line
Protective cover
Slave
LED indicators
Expansion connector
Ch-to-Ch non-isolated
[How to Connect AnyWireASLINK]
The AnyWireASLINK can employ a two-wire or four-wire terminal selectively depending
on the load current. If the load current is small, using a two-wire (non-isolated) terminal
allows for achieving simpli ed wiring without local power supply.
In the case of prioritizing the sites of concentrated loads and/or the number of
connections, hybridization with a four-wire (isolated) terminal, which supports local
power supply, is also possible.
Make sure to use a four-wire (isolated) terminal in the case of input and load driving
using an external power supply.
[System Configuration Example]
■Connection with 2-wire (non-isolated) terminals only
AnyWireASLINK
master
*
24V DC
*
Make sure to use a
24V DC stabilized
power supply for the
power supply to be
connected.
*
When complying with
the UL Standard, make
sure to use a 24V DC
stabilized power supply
of "NEC Class 2
Output."
General-purpose
cabtyre cable
Dedicated at cable
1.25mm
(2-wire)
2
2P link connector is
convenient for
branching.
The sum of the
portions of DP, DN is
the total line length.
Black: DN
■Relationship between the size and length of
the transmission line and the supply current (Table 1)
Size of
the transmission
line (DP, DN)
1.25mm
2
0.75mm
2
0.5mm
2
CAUTION
- Connect the same symbols (DP, DN) correctly between the AnyWireASLINK
master unit and each device.
- The branching length or branch number has no limitation.
- Include the length of the cable provided with the terminal in the "total line length."
- Connect the terminator (with polarity) on the transmission line terminal farthest
from the AnyWireASLINK master unit.
-L*D*1AW 3/14-
Red:
Red: DP
DP
2 points
Black:
Black: DN
DN
Red: DP
2 points
Black: DN
Red: DP
1 point
Black: DN
Red: DP
1 point
Black: DN
Red: DP
16 points
Black: DN
The branching
has no limitation.
Red: DP
AnyWireASLINK terminator
One terminator should be connected to the DP, DN
terminal farthest from the AnyWireASLINK master unit.
Connect it correctly so as not to set the wrong polarity.
Supply current on the transmission line (DP, DN)
Total length:
Total length: Over 50m,
50m or less
no longer than 100m
MAX 2A
MAX 1A
MAX 1.2A
MAX 0.6A
MAX 0.8A
MAX 0.4A
- Refer to Table 1 so that the size and length of the transmission
line and the allowable supply current lie within an appropriate
range.
2 points
Black: DN
2 points
Red: DP
2 points
Red: DP
Black: DN
2 points
Total length: Over 100m,
no longer than 200m
MAX 0.5A
MAX 0.3A
MAX 0.2A