7.7
Setting up the correction of values indicated by the module 'SC'
The AVM 1002D module is designed to work with ICP® (IEPE) accelerometers with sensitivity of 100
mV/g, however it is possible to set up set correction of values indicated by the module to adjust the
module to a sensor with sensitivity slightly different than 100 mV/g. The 'SC' parameter indicates how
much the presented values are being increased or decreased.
To set correction of values indicated by the module one should perform the following procedure:
1. Press UP/DN. Afterwards the OK LED will blink rapidly, which indicates entering into the
device menu.
2. By pressing UP/DN set the 'SC' on the display.
3. Confirm by pressing the SET button.
4. Use the UP/DN buttons to select the desired correction value within the -10 up to +10
range. Negative values are indicated by glowing decimal point on the right display.
5. To confirm the change, press the SET button.
7.8
Turning display off on sensor failure 'Er'
The module enables to mask the incorrect measurement values in the case of sensor circuit failure.
Activating this feature results in display of the "--" symbol in the case of open or short circuit.
To enable the feature one should perform the following procedure:
1. Press UP/DN. Afterwards the OK LED will blink rapidly, which indicates entering into the
device menu.
2. By pressing UP/DN set the 'Er' on the display.
3. Confirm by pressing the SET button.
4. Use the UP/DN buttons to select the ON option.
5. To confirm the change, press the SET button.
To disable the feature one should perform the following procedure:
1. Press UP/DN. Afterwards the OK LED will blink rapidly, which indicates entering into the
device menu.
2. By pressing UP/DN set the 'Er' on the display.
3. Confirm by pressing the SET button.
4. Use the UP/DN buttons to select the 'oF' option.
5. To confirm the change, press the SET button.