Display and Keyboard Operation
Remark: "SET": Start/stop, (backspace)
"△" : "+",Plus 1
"▽" : "-" , Minus 1
"ENT": "ENTER" (call out setting parameter)
6.1 Parameter Setting Sequence
Please insure that the motor is under the stop situation when set the parameter. That is, in the case of panel
mode, the motor is in the stop state or an external port mode, the motor is enabled to disconnect
1. In standby condition, press "ENTER" to call out the system parameters, press "ENTER" again, it will call out the
parameter value.
2. Press "△"or "▽" to the parameter number. Press "SET" to return to standby mode if there is no need to change
value.
3. Press "ENTER" to show the parameter setting value. Press "SET" to return to standby mode if there is no need
to change value.
4. Press"△"or "▽" to the value demanded.
5. Press "ENTER" to save the changes, then press "SET" to return to standby mode.
Note: At setting mode, it will return to display interface if there is no press within one minute.
6.2 Working mode
Motor works at two modes. One is the panel mode; the other is external terminal control. The motor runs as the
setting, LED digital display shows the speed of motor. Under the panel mode, Press "SET" to start/stop the motor,
long press "△"or "▽" to acceleration or deceleration speed, press "ENTER" to insure and know the running speed.
The motor runs as setting speed.
6.3 Protect mode
While Motor operates abnormally, display will show ERR×
(1) Err-01: stall
(2) Err-02: over current
(3) Err-04: hall fault
(4) Err-05: stall and hall fault
(5) Err-08: under-voltage
(6) Err-10: over-voltage
(7) Err-20: peak current alarm
(8) Err-40: temperature alarm