American Rotary AD 25 Betriebs- und Installationshandbuch - Seite 3

Blättern Sie online oder laden Sie pdf Betriebs- und Installationshandbuch für Medienkonverter American Rotary AD 25 herunter. American Rotary AD 25 15 Seiten. Adx-cul cnc/heavy duty rotary phase converters

Electric shock could result in death or injury. Please
consult qualified personnel for installation.
DANGER: Risk of Electric Shock
Please wait 30 minutes before servicing
This manual is to serve the purpose of providing recommendations for proper performance
but is not to supersede or replace local or national electric codes. Installation should be done
by a licensed electrician who is familiar with phase converter installations.
WARNING! READ BEFORE STARTING CONVERTER!
If this phase converter does not start in less than 2 seconds, TURN IT OFF!
1.
Make sure the wire size meets our minimum recommended size.
2.
All loads INCLUDING TRANSFORMERS must be DISCONNECTED before starting the phase converter
each time. This includes small control transformers that run controls inside your equipment. If you need an
economical 3-phase disconnect switch, please visit
for assistance.
If your converter still takes more than 2 seconds to start, call our Toll-Free Technical support line 1-888-743-
6832. You will be asked to verify conditions 1 and 2 above are met. Failing to meet these two conditions
account for 99% of starting problems and can result in damage to the starting capacitors.
This converter is quiet. If it does not sound quiet and smooth, TURN IT OFF!
3.
Make sure the idler motor is mounted on rubber. DO NOT BOLT THE IDLER MOTOR DOWN! This can
cause bearing failure.
4.
Make sure the idler motor is wired properly.
For the American Rotary/Baldor soft-start idler motor
240 Volts Input (1, 7, A), (2, 8, B), (3, 9, C), (4, 5, 6 bolted together and insulated).
480 Volts Input (1, A), (2, B), (3, C). The following bolted together and insulated: (4, 7), (5, 8), (6, 9)
Do not ground any of these connections! Use the supplied bolts and make sure all connections
are insulated. Do not use wire nuts. See pages 8-9 for more in depth instructions.
Failure to wire the idler motor properly will void warranty!
* Make sure the Phase Converter Panel, the Idler Motor, and your equipment is grounded!
5.
This phase converter does NOT disconnect the single phase power as it passes through the unit, so the
single phase legs remain energized even when the rotary phase converter is off. In addition to installing a
single phase breaker in front of the phase converter, you need to be aware that the single phase power
DOES flow through the phase converter whether the unit is on or off.
6.
Before connecting load, verify proper function of phase converter. This will ensure the protection of the
phase converter and your equipment.
For a stock three-phase motor that uses our Stock Motor Panel, wire
the motor according to the diagram for that motor, NOT according to our wiring diagram.
DANGER: HIGH VOLTAGE
www.AmericanRotary.com
or call 1-888-743-6832
2