Warning! In order to supply the KNX bus lines use
only KNX bus power supplies (e.g. ekinex EK-AB1-
TP or EK-AG1-TP). The use of other power supplies
can compromise the communication and damage
the devices connected to the bus.
Configuration and commissioning
Configuration and commissioning of the device require
the use of the ETS
(Engineering Tool Software) program
®
V4 or later releases. These activities must be carried out
according to the design of the building automation system
done by a qualified planner.
i
Note. The configuration and commissioning of KNX
devices require specialized skills. To acquire these
skills, you should attend the workshops at KNX cer-
tified training centers.
Configuration
For the configuration of the device parameters the corre-
sponding application program or the whole ekinex
duct database must be loaded in the ETS program. For
detailed information on configuration options, refer to the
application manual of the device available on the website
www.ekinex.com.
Product
Application program
code
(## = release)
EK-E12-TP
APEKE12TP##.knxprod
EK-E22-TP
APEKE22TP##.knxprod
Commissioning
For commissioning the device the following activities are
required:
• make the electrical connections as described above;
• turn on the bus power supply;
• switch the device operation to the programming mode
by pressing the programming pushbutton located on
the front side of the housing. In this mode of operation,
the programming LED is turned on;
• download into the device the physical address and the
configuration with the ETS
At the end of the download the operation of the device
automatically returns to normal mode; in this mode the
programming LED is turned off. Now the bus device is
programmed and ready for use.
Reset of the device
To reset the device remove the bus connection by ex-
tracting the bus terminal from its seat. Keeping pressed
the programming pushbutton, reinsert the bus terminal in
his seat; the programming LED blinks fast. Release the
programming button and remove the bus terminal again;
the reset was carried out. Now you need to address and
configure again the device via ETS.
!
Warning! The reset restores the device back to the
state of delivery from the factory. The address and
the value of the parameters set during configuration
will be lost.
pro-
®
Communica-
Group
tion objects
adresses
(nr. max)
(nr. max)
222
222
222
222
program.
®
Dimensions [mm]
Pushbutton for round wall box
Versions
for mounting with frame
for mounting without frame
Pushbutton for rectangular wall box
L
Versions
for mounting with frame
for mounting without frame
2,5
29
29
2,5
5
21
13
9
L
Dimensions L x H [mm]
81 x 77
80 x 80
12
Dimensions L x H [mm]
122 x 77
121 x 80
Rockers
2,5
58
2,5
58
21
9