The pushbutton has to be mounted on a round or square
flush-mounting box with distance between fixing holes of
60 mm. If necessary, the metallic support for mounting
on the wall box can also be ordered separately using the
code EK-SMQ-71.
i
Note. Programming pushbutton and LED are ac-
cessible from the front side of the device. It is better
addressing the device before the final assembly of
rockers and frame. Once the addressing has been
performed, the device configuration can be later
downloaded without pressing the programming pu-
shbutton.
Mounting position
If the integrated sensor is used for temperature regulation
(EK-ED2-TP versions only), the device has to be installed
preferably lon an internal wall at the height of 1,5 m and
at least 0,3 m far from doors. The device can not be instal-
led close to heat sources such as radiators or houshold
appliances or in position subjected to direct sunlight. If
necessary, for the regulation can be used a weighted ave-
rage value between the value measured by the integrated
sensor and a value received via bus by another KNX de-
vice.
Use as a room temperature controller (EK-ED2-
TP versions only)
The pushbutton can be also used as a room temperature
controller for single-stage heating/cooling systems with
radiators, radiant panels and electrical heaters. As the de-
vice has no user interface, it must receive the operational
parameters by the bus (e.g. operating mode, seasonal
conduction mode or a change of the setpoint value).
Main functional characteristics (room temperature con-
troller)
• Temperature measuring through integrated sensor with
possibility of sending the value on the bus
• 2-point (on/off) or proportional (PWM or continuous)
room temperature regulation
• Seasonal conduction modes: heating and cooling with
possibility of changeover via bus or automatic depen-
ding on the configuration
• Operating modes: comfort, standby, economy and bu-
ilding protection with different setpoint for heating and
cooling
• Automatic switching of the operating modes triggered
by window opening/closing
• Weighted average of two temperature values
• Temperature control alarm
• Anti-locking function for valves (hydronic systems)
Switching, display and connection elements
The device is equipped with four mechanisms for
switching, four LEDs for each channel (EK-ED2-TP ver-
sione only), a programming LED and a programming pu-
shbutton (on some versions only) and a terminal block for
connection of the bus line.
min 0,3 m
1,50 m
Switching elements
• Pushbutton (7) for switching between the normal and
programming operating modes (on some versions only)
• One, two or four rockers (4) for independent switching
of single or group of loads
Display elements
• Red LED (8, on some versions only) for indication of
the active operating mode (on = programming, off =
normal operation)
• Freely programmable LED with lightguide (5) e.g. for
feedback status and orientation nightlight LED (for EK-
ED2-TP versions only).
1
2
4
5
6
1) Connection terminal block for KNX bus line
2) Product label
3) Adapter
4) Rocker (in the example: 30 x 30 mm square type)
5) LED-lightguide
6) Positioning of the temperature sensor
7) Programming pushbutton (on some versions only)
8) Programming LED (on some versions only)
Connection of the KNX bus line
The connection of the KNX bus line is made with the ter-
minal block (black/red) included in delivery and inserted
into the slot of the housing.
Characteristics of the KNX terminal block
• spring clamping of conductors
• 4 seats for conductors for each polarity
• terminal suitable for KNX bus cable with single-wire
conductors and diameter between 0.6 and 0.8 mm
• recommended wire stripping approx. 5 mm
• color codification: red = + (positive) bus conductor,
black = – (negative) bus conductor
!
Warning! The electrical connection of the device
can be carried out only by qualified personnel. The
incorrect installation may result in electric shock or
fire. Before making the electrical connections, make
sure the power supply has been turned off.