DALI bus line connections
The connection to the DALI bus network is done via the
spring clamp terminal, located on the front of the device
in the upper part.
The length and type of the connection cables to the DALI
bus must be compliant with the protocol specification and
the present regulations and they should be isolated from
every wiring or parts at voltage not SELV. Use double in-
sulated shielded and twisted cables.
All the devices connected to the DALI bus must be SELV
(the devices connected must be SELV or supply a SELV
signal).
INSTALLATION TECHNICAL NOTES
• Installation and maintenance must be
performed only if the power supply has
been turned off.
• Installation and maintenance must only
be performed by qualified personnel in
compliance with current regulations.
• The product must be installed inside a
wall mounting box or an electrical panel,
where it is recommended to install a sur-
ge protector.
• The product must be protected by a sui-
tably sized fuse.
• The product must be protected by a su-
itably sized magnetothermic switch on
the main input line.
• The product must be installed in a verti-
!
cal position with the front / label facing
the front or in a horizontal position with
the front / label facing upwards. Other
product installation positions are not al-
lowed.
• Do
not
connect
Do
not
connect
ruptible
power
tput
other
The device is not grounded. Protection
from accidental contacts is guaranteed
by the casing.
• Use in thermally harsh environments
could limit the output power.
• In the system, keep the 90-230Vac circu-
its and the non-SELV circuits separate
from the SELV circuits at very low safety
voltage and from the DALI bus
• It is absolutely forbidden to connect, for
any reason whatsoever, directly or indi-
rectly, the 90-230Vac mains voltage to
the DALI bus or to the loads.
• Use double insulated cables.
Characteristics of the DALI terminal block
• Spring tightening of the conductors
• Command and bus wiring: 0.05 mm
stranded – 30 - 16 AWG
• Conductor stripping recommended: 5.0 - 6.0 mm
• Length of connection cables < 25 m
inductive
loads.
to
UPS
(uninter-
supply)
with
ou-
than
Pure
Sine
Wave.
solid – 1.5 mm
2
Connection of power supply and loads
The connection to the 90-230 Vac 50-60Hz power supply
is done via the spring terminals, located in the lower part
of the device.
Characteristics of the supply and loads terminal block
• Spring tightening of the conductors
• Power and loads wiring: 1.5 mm
ded – 16 - 13 AWG
• Stripping recommended approx.: 5.0 - 6.0 mm
Output
The cables connected to the outputs must be correctly
sized and must be isolated from any wiring or parts with
different voltages. The length and type of connection ca-
bles must comply with the regulations in force.
Configuration and commissioning
Configuration and commissioning activities of the device
must be carried out according to the design of the building
automation system done by qualified planners.
For commissioning the device the following activities are
required:
• make the electrical connections as indicated above;
• power up the supply and the DALI bus;
• carry out the device programming via a DALI interface.
By holding down the button relating to a channel, a test
is carried out on the connected load, which lights up and
flashes for 1s.
Installation diagrams
The device can be installed by wiring the outputs with ei-
ther a separate COM pole or a common COM pole. The
following schemes can be implemented:
1. Outputs with separate COM pole connection
DALI
2
L
90-230 Vac
50-60 Hz
N
Installation diagram with outputs with
separate COM pole connection
3
solid – 2.5 mm
stran-
2
2